After generation of electricity it is important to
transform that voltage at user end/ load end.
Reason 1 for Transmission at Higher voltage
During transmission there are losses known as
Transmission losses as heat get generated during transmission, Usually this
loss is known as heat loss.
Heat loss is = I2R
When Transmission is done at High voltage then Current
drawn will get reduced as:-
Transmission power= Voltage X Current X Power factor
Now Current= Transmission
Power
Voltage X Power
factor
From above you will see that higher the transmission
voltage, lower will be the Current so lower will be I2R losses.
Now let’s take an example; For Power transmission at
11 KV and 33 KV for power of 1 MW, in both cases resistance will be same so
only variable is Transmission voltage.
Current(11KV) = Transmission power (1 MW) ---------- (i)
11 KV X Power
factor
Current (33 KV) = Transmission power (1 MW) --------- (ii)
33 KV X Power
factor
Now Heat loss (11 KV)= (Transmission power (1 MW))2 --------- (iii)
( 11 KV X Power factor)2
Heat loss (33 KV)= (Transmission power (1 MW))2
------------- (iv)
( 33 KV X Power factor)2
Now divide (iii) by (iv)
Heat loss (11KV) = (33 KV)2
Heat Loss (33 KV) (11 KV) 2
Now Heat loss (11 KV) = 9
times the heat loss at 33 KV ---- (v)
You will see how big
difference it will be.
Reason 2
for Transmission at Higher voltage
There is one another reason for transmission
at Higher voltage is weight. When Transmitting voltage at low levels then
in order to reduce the transmission losses there is often practice to use
conductor of big diameter as Resistance is inversely proportional to conductor
diameter, so larger the diameter lower will be the resistance of conductor. So
lower will be the transmission losses. This will leads to higher weight of
conductor. Now when Transmission is done at higher voltage conductor with
smaller diameter will be sufficient as thinner wire will have to transmit lower
currents.
As conductor is lower this will lead to
smaller snags and leads to more savings. This will also leads to lower number
of towers.
Let’s illustrate this with an example; Now from equation (v)
Heat loss at 11 KV= 9
times the heat loss at 33 kV
Now for same current resistance is to be reduced.
Now
resistance = Resistivity X Length
Area
Now Area is directly proportional to square of
conductor radius/diameter
So
for same heat loss at 11 KV conductor area must be increased to 3 times the conductor
for 33 KV.
You
can see that how there are advantages of transmitting the power at Higher
voltage.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.