Transformers are backbone of electrical systems.
Transformers are used for both stepping up and stepping down the voltage. While
procurement of Distribution Transformers
there are following technical aspects which should be considered :-
For Tan-delta, Loss angle test visit link:-
http://electrialstandards.blogspot.com/2015/10/tan-delta-test-loss-angle-test.html
Below are the technical specifications of Oil type 990 KVA transformer :-
1.
Transformer voltage ratio should be 11 KV/ 433 V
2.
Vector group should be Dyn11
3.
Transformer Impedance at 75 degree Celsius should
be 5%
4.
Transformer maximum no load losses should 1.4 KW
5.
Transformer Maximum full load losses should be
10.8 KW
6.
Transformer Oil Temperature rise without
enclosure should be 35 Deg C max over ambient 40 Deg C
7.
Transformer Winding Temperature rise without
enclosure should be 40 Deg C max over
ambient 40 Deg C
8.
Current density of LT and HT winding should be
3 A/mmsq
9.
Tapping on HT winding should be off load with +/- 5% in 2.5% step
10.
Design
clearances for Phase to phase for 11 KV system should be 180 mm and Phase to
earth for 11KV system should be 120 mm
11.
Design clearances for Phase to phase for 433 KV
system should be 25 mm and Phase to earth for 433KV system should be 25 mm
12.
Transformer
Type should be Double
Copper wound, three phase, oil immersed, with ONAN cooling
13.
Voltage
variation on Supply side should be +/- 10%
14.
Frequency
variation on Supply Side should be +/- 5%
15.
Insulation level
for one minute power frequency withstand voltage should be 3KV for 433V system
& 28KV for 11KV system
16.
Insulation level for Lightning
impulse withstand voltage should be 75KV peak for 11KV system
17.
Short circuit
withstand level should be 3 Sec with 5% impedance
18.
Noise level for
Transformer should not exceed limits as per NEMA TR-1 with all accessories
running measured as per IEC 551 / NEMA standard running measured as per IEC 551
/ NEMA standard
For Transformer Oil Filteration process visit link:-
http://electrialstandards.blogspot.in/2015/10/transformer-oil-filtration-process.html
For Transformer Oil Filteration process visit link:-
http://electrialstandards.blogspot.in/2015/10/transformer-oil-filtration-process.html
19.
Transformer tank design should be as below:-
Tank
|
Type
Tested Design
|
|
Design
|
a)
Completely sealed type with corrugated fins and with/without conservator tank
as per site requirements
b) Completely oil filled or N2 cushion at
top filled with positive pressure. N2 shall be technical grade in accordance
with IS:1747
c) With bolted / welded cover
|
|
Plate
/ Corrugated fin / tank features
|
a)
Adequate for meeting mechanical & electrical withstand requirements, as
per applicable standard.
b)
The tank and its sealing (gaskets, o-rings, etc.) shall be of adequate
strength to withstand positive and negative pressures built-up inside the
tank while the transformer is in operation. The maximum pressure generated
inside the tank should not exceed 40kPa, positive or negative.
c)
Corrugated fins shall be built up of CRCA sheets of minimum 1.2mm thick.
d)
The corrugated tank wall shall ensure sufficient cooling of the transformer and
compensate for the changes in the oil volume during operation.
e) The transformer shall be capable of
giving continuous rated output, without exceeding the specified temperature
rise.
f)
Internal clearance of tank shall be such that, it shall facilitate easy
lifting of core with coils from the tank and HV & LV bushings mounted on
Top cover.
g) All joints of tank and fittings shall be
oil tight. The tank design shall be such that the core and windings can be
lifted freely with cover. The tank plate shall be of such strength that the
complete transformers when filled with oil may be lifted bodily by means of
lifting lugs.
h)
Tanks with corrugations & without conservator shall be tested for leakage
at a pressure as per the applicable standard.
|
|
Material
of Construction
|
Mild
steel plate with low carbon
|
|
Plate
Thickness
|
To
meet the requirements of pressure and vacuum type tests as per CBIP manual
|
|
Welding
features
|
a)
All seams and joints shall be double welded
b)
All welding shall be stress relieved for sheet thickness greater than 35 mm
c)
All pipes, stiffeners, welded to the tank shall be welded externally
d) All corrugated fins or expansion bellows
provided shall be double welded.
|
|
Tank
features
|
a)
Bottom with stiffeners & adequate space for collection of sediments
b)
No external pocket in which water can lodge
c)
Tank bottom with welded skid base
d)
Strength to prevent permanent deformation during lifting, jacking,
transportation with oil filled.
e) Minimum
disconnection of pipe work and accessories for cover lifting
f) Tank to be designed for oil filling under
vacuum g) Tank cover fitted with lifting lug
|
20.
Transformer oil should be Class 1 new mineral insulating oil, shall be
certified not to contain PCBs. Naphthalene base with antioxidant inhibitor.
21.
Transformer winding should have following:-
Winding
|
||
Material
|
Electrolytic
Copper
|
|
Maximum
Current Density allowed
|
Maximum
3 amp / sqmm
|
|
Winding
Insulating material
|
Class
A, non catalytic, inert to transformer oil, free from compounds liable to ooze
out, shrink or collapse.
|
|
Winding
Insulation
|
Uniform
|
|
Design
features
|
a)
Stacks of winding to receive adequate shrinkage treatment.
b)
Connections braced to withstand shock during transport, switching, short
circuit, or other transients.
c) Minimum out of balance force in the
winding at all voltage ratios.
d)
Conductor width on edge exceeding six times its thickness.
e)
Transposed at sufficient intervals.
f) Coil assembly shall be suitably supported
between adjacent sections by insulating spacers + barriers.
g)
Winding leads rigidly supported, using guide tubes if practicable.
h) Winding structure & insulation not to
obstruct free flow of oil through ducts.
i)
Delta connection shall be done using Flexible cable.
|
22.
Transformer Bushings and Terminations should
have following technical specifications:-
Bushings
and Terminations
|
||
Type
of HV side bushing
|
Epoxy
cast bushing, 630 Amp, interface type ‘C’ as per EN50180 and EN50181.
|
|
Type
of LV side bushing
|
Indoor,
Epoxy resin cast, 1kv voltage class and creepage 31mm/KV
|
|
Essential
provision for LV side line bushing
|
It
shall be complete with copper palm suitable for tinned copper busbar of size
100x12 mm
|
|
Essential
provision for LV side neutral bushing
|
In
case of neutral bushing the stem and bus bar palm shall be integral without
bolted, threaded, brazed joints. Bus bar size shall be 100x12 mm
|
|
Arcing
Horn
|
As
per site requirements
|
|
Termination on HV side bushing
|
Cable
connection by screened separable connector kit.
|
|
Termination of LV side bushing
|
Bus
bar connections
|
|
Minimum creepage distance of all bushings and
support insulators.
|
31mm/kv
|
|
Protected creepage distance
|
At
least 50 % of total creepage distance
|
|
Continuous Current rating
|
Minimum
20 % higher than the current corresponding to the minimum tap of the
transformer
|
|
Rated thermal short time current
|
26.3kA
for 3 sec
|
|
Bushing terminal lugs in oil and air
|
Tinned
copper
|
23.
Current Transformers used for Transformers
should have following Technical specifications:-
Current Transformers
|
All
three phases and neutral on LV side
|
Maintenance requirements
|
Replacement
should be possible by removing fixing nut of mounting plate without
disturbing LT bushing
|
Accuracy Class
|
5P10
|
Burden
|
5VA
|
Type
|
Resin
Cast Ring type suitable for outdoor use
|
CT ratio
|
990KVA -1500/5 Amp
|
24.
Transformer Name plate should consists of
following Parameters:-
For Parallel Operation of Transformers Visit link:-
http://electrialstandards.blogspot.com/2015/10/parallel-operation-of-transformers.html
For Parallel Operation of Transformers Visit link:-
http://electrialstandards.blogspot.com/2015/10/parallel-operation-of-transformers.html
Following details shall
be provided on rating and diagram plate as a minimum.
a) Type/kind
of transformer with winding material.
b) IS/
IEC [R3] standard to which it is manufactured.
c) Manufacturer's name.
d) Transformer serial number.
e) Month and year of manufacture.
f) Rated frequency in HZ.
g) Rated voltages in KV.
h) Number
of phases.
i)
Rated power in KVA.
j)
Type of cooling (ONAN).
k) Rated
currents in Amp.
l)
Vector group connection symbol.
m) 1.2/50µs
wave impulse voltage withstands level in KV.
n) Power
frequency withstands voltage in KV.
o) Impedance
voltage at rated current and frequency in percentage at principal, minimum and
maximum tap
p) Load
loss at rated current.
q) No-load
loss at rated voltage and frequency
r) Continuous ambient temperature at which
ratings apply in deg c
s) Top
oil and winding temperature rise at rated load in deg c;
t)
Winding connection diagram with
taps and table of tapping voltage, current and power
u) Transport
weight of transformer
v) Weight
of core and windings
w) Total
weight
x) Volume
of oil
y) Weight of oil
z) Name
of the purchaser
25. Transformer
to be designed for suppression of 3rd, 5th, 7th harmonic voltages and high
frequency disturbances
26. Transformer
core should have following technical specifications:-
Core
|
|
Grade
|
High
grade , non- ageing, low loss, high permeability, grain oriented, cold rolled
silicon steel lamination
|
Core
Design Features
|
a)
Magnetic circuit designed to avoid short circuit paths within core or to the
earthed clamping structures.
b)
Magnetic circuit shall not produce flux components at right angles to the
plane of lamination to avoid local heating.
c) Least possible air gap and rigid clamping
for minimum core loss and noise generation.
d)
Adequately braced to withstand bolted faults on secondary terminals without
mechanical damage and damage/ displacement during transportation and
positioning.
e) Percentage harmonic potential with the
maximum flux density under any condition limited to avoid capacitor
overloading in the system.
f) All steel sections used for supporting
the core shall be thoroughly sand blasted after cutting, drilling, welding.
g)
Provision of lifting lugs for core coil assembly.
h)
Supporting framework designed not to obstruct complete drainage of oil from
transformer
|
http://electrialstandards.blogspot.com/2015/10/parallel-operation-of-transformers.html
For Tan-delta, Loss angle test visit link:-
http://electrialstandards.blogspot.com/2015/10/tan-delta-test-loss-angle-test.html
Very useful information about transformers.
ReplyDelete11kv current transformer
Very useful information you shared with us. thank you for sharing this information.
ReplyDeleteTate Electricals is one of the best transformer manufacturers in Pune.
Thanks for Sharing such an informative post, Good work and great stuff. Access us to know more about Transformers
ReplyDeleteTransformer Manufactuerers In Pune
Transformer Manufactuerers In Mumbai
Transformer Manufactuerers In India