Search This Blog

Wednesday, September 3, 2025

IS 3043:1987 Simplified version relevant to Industries

 Based on the document IS 3043: 1987 - Code of Practice for Earthing, here are some of the key values and formulas relevant to an electrical engineer.

Formulas and Calculations

  • Earth Fault Current (Iₑ):

    The standard defines the earth fault current as the current that flows through the earth connection. For a line-to-earth fault, the current is given by:

    I(f)​=Vp​/ (Ze + Zp)​​

    Where:

    • I(f) is the earth fault current.

    • Vp is the phase voltage.

    • Zp is the phase impedance.

    • Ze is the earth fault loop impedance.



  • Earth Electrode Resistance (Re​):

    The document provides a simplified formula for the resistance of a single vertical rod electrode:


    Where:

    • Re is the earth resistance in ohms.

    • p is the soil resistivity in ohm-meters.

    • l is the length of the electrode in meters.

    • d is the diameter of the electrode in meters.

Specified Values

Touch Voltage and Clearance Time: The document specifies the maximum permissible touch voltage () that can be sustained for a certain duration before the circuit must be cleared. The formula for the maximum permissible touch voltage is: 



Where:

  • is the maximum permissible touch voltage in Volts.

  • is the clearing time in seconds.

  • Earth Fault Current Duration:

  • The standard recommends specific time durations for earth fault currents to be considered in design:

    • For substations at 66 kV and above, the duration should be taken as 1.0 second.

    • For all other voltage levels below 66 kV, the duration should be taken as 3.0 seconds.

  • Corrosion Allowance:

    The document provides a table for the average corrosion rates of steel and copper in different soil conditions. It states that, on average, steel corrodes about 6 times faster than copper in soil. The standard recommends specific allowances for corrosion to ensure the long-term integrity of the earthing system.

  • Residual Current Devices (RCDs):

    For portable and mobile generators, the standard recommends using RCDs with a fast operating time. The specified tripping characteristics are:

    • Operating time of 40 milliseconds or less.

    • Operating current of 250 mA.

No comments:

Post a Comment

Note: Only a member of this blog may post a comment.