Induction motors not kept running in Star Connections
Why Induction Motors Are Not Kept Running in Star Connection
Induction motors are sometimes started in Star connection (using a Star-Delta starter) but are always run in Delta for normal operation. The reasons are:
1. Voltage Reduction in Star
-
In Star connection,
-
This means each winding receives only 57.7% of the line voltage.
2. Current Reduction
-
Since , the line current drawn is lower.
-
Current is reduced in proportion to the reduced voltage.
3. Torque Reduction
-
Motor torque is proportional to the square of the applied voltage:
-
So, in Star:
-
This means the motor can produce only one-third of the rated torque.
4. Power Reduction
-
Motor input power is proportional to voltage × current.
-
Because both are reduced in Star, the motor delivers only about one-third of its rated power compared to Delta.
5. Inefficiency & Underutilization
-
Running in Star keeps the motor underloaded, unable to handle its designed mechanical load.
-
Efficiency and performance drop significantly.
-
That’s why Star is used only for starting, to limit inrush current, and then switched to Delta for normal running.
✅ Conclusion:
Induction motors are not kept running in Star connection because they deliver only one-third torque and power, making them inefficient and unsuitable for normal operation. Hence, Star is used for starting only, while Delta is used for continuous running.

MRS Agencies is a TOP Copper Bonded Chemical Earthing Electrode Manufacturers in India. Our is a professionally-managed organization that guarantees the high quality of our product variety is maintained thoroughly. We can also customize these Pure Copper Earthing Electrode, Chemical Earthing/ Gel Earthing Electrode, Chemical Pipe Earthing Electrode, Lightning Arrester, products as per requirements detailed down by the clients.