Earthing is used to protect both human and equipment's from abnormal currents.
These abnormal currents will get
dissipated safely when properly conducted to earth via the electrode.
There are three components to the
resistance:-
1. Resistance of
the electrode materials
2. Contact
resistance between the electrode and the soil surrounding it
3. Resistance of
the surrounding earth.
The contact resistance between
earth and the electrode is minimal if the electrode materials Cleaned properly
and unpainted. Even if steel get rusted
even then rusted steel ground rods have little contact resistance because the
iron oxide readily soaks up water and has less resistance than most soils. It
has been found that the resistance of the surrounding earth will be the largest
of the three components as described above.
A proper earthing system
generally works on the system that an earth electrode system buried in the earth
radiates current in all directions which will get dissipated at some distance
away depending on the soil’s resistance to current flow which is also known as
soil resistivity.
Earthing system consists of multiple electrodes
buried at distance and are connected in parallel and a grid is formed so as to minimize
grid resistance and whenever fault occurs that fault current will flow through
grid and ultimately get dissipated.
Generally an earth electrode can be thought of as
being surrounding by shells of earth, each of the same thickness as shown below.
The shell closest to the electrode has the smallest surface area and offers the
greatest resistance as resistance is inversely proportional to area. The next
shell has larger area then nearest shell so it has lower resistance, and so on.
A distance eventually will be reached where the additional earth shells do not
add significantly to the resistance.
Earth electrode resistance is measured to remote
earth, which is the earth outside the electrode’s influence. A larger electrode
system requires greater distance before its influence decreases to a negligible
level.
Measuring
Earth pit Resistance
Earth pit resistance is measured by using earth pit
tester. Which are shown below:-
There is following process by which earth pit resistance can be measured. There are four terminals in earth pit tester described as ;
There is following process by which earth pit resistance can be measured. There are four terminals in earth pit tester described as ;
C1 & C2 known as current terminals, P1 & P2
known as potential terminals.
One current terminal (C1) is
connected to the earth electrode under test and the other (C2) to a probe
driven in the earth some distance away. The test set injects a current into the
earth between the two current terminals. One potential terminal (P1) also is
connected to the earth electrode but the other potential terminal (P2) is
connected to a separate probe driven in the earth between the electrode and the
current probe (C2). The potential probes detect the voltage due to the current
injected in the earth by the current terminals. The test set measures both the
current and the voltage and internally calculates and then displays the
resistance
Resistance= Voltage/ Current
When measuring the resistance of
earth electrode systems generally fall of potential method is used.
Fall of Potential Method:-
This method is most widely used to measure earth pit
resistance. Procedure for the same is discussed below:-
The basic procedure for the Fall-of-Potential method
is to first connect the test set terminals C1 and P1 to the earth electrode
under test, connect the test set C2 terminal to a current probe located some
distance from the earth electrode and finally connect the test set P2 terminal
to a potential probe located a variable distance between. The two probes
normally are located in a straight line. At each potential probe location, the
resistance is recorded (a form is provided in
1. Connect C1 and P1 terminals on the test set to
the earth electrode as shown in fig below
2. Drive a probe into the earth 100 to 200 feet from
the center of the electrode and connect to terminal C2. This probe should be
driven to a depth of 6 – 12 inches.
3. Drive another probe into the earth midway between
the electrodes and probe C2 and connect to terminal P2. This probe should be
driven to a depth 6 – 12 inches.
4. Record the resistance measurement.
5. Move the potential probe 10 feet farther away
from the electrode and make a second measurement.
6. Move the potential probe 10 feet closer to the
electrode and make a third measurement.
7. If the three measurements agree with each other
within a few percent of their average, then the average of the three
measurements may be used as the electrode resistance.
8. If the three measurements disagree by more than a
few percent from their average, then additional measurement procedures are
required.
Thanks for sharing this valuable information. You have posted a trust worthy blog keep sharing. Nice article i was really impressed by seeing this article, it was very interesting and it is very useful for me. CONTACT RESISTANCE TESTER
ReplyDeleteThank you for sharing the valuable content.
ReplyDeleteJost’s material handling provides innovative solutions for internal material handling needs for its customers so that it improves the efficiencies of their processes.
electrical testing and measurement