Transformer Percentage impedance; Importance of Transformer impedance; Calculating Transformer Impedance

Percentage Impedance of a Transformer (Z%)

The percentage impedance (Z%) of a transformer is one of the most important parameters marked on its nameplate. It influences voltage regulation, fault levels, and load sharing when transformers are connected in parallel.




Definition

The percentage impedance of a transformer is:

  • The voltage drop at full load caused by the resistance and leakage reactance of the windings, expressed as a percentage of the rated voltage.

  • Alternatively, it can be defined as the percentage of rated terminal voltage required to circulate full-load current under short-circuit conditions.


Measurement of Transformer Impedance

Transformer impedance is measured by performing a short-circuit test:

  1. One winding of the transformer is short-circuited.

  2. A reduced voltage (at rated frequency) is applied to the other winding.

  3. The voltage is gradually increased until the rated full-load current flows through the windings.

The percentage impedance is then calculated as:

Z%=VSCVRated×100Z\% = \frac{V_{SC}}{V_{Rated}} \times 100

Where:

  • VSCV_{SC} = Short-circuit voltage (the applied voltage required to circulate full-load current)

  • VRatedV_{Rated} = Rated voltage of the transformer


Design Factors Affecting Impedance

The natural impedance of a transformer depends on leakage flux, which is influenced by:

  • Winding ampere-turns

  • Leakage flux path length and area

  • Geometric arrangement of windings

  • Volts per turn

By altering these design parameters, manufacturers can increase or decrease the impedance as per system requirements.


Effect of Transformer Impedance on Fault Levels

The impedance value directly influences the fault current during system short circuits.

Example:
For a 5 MVA transformer with 5% impedance, the maximum fault MVA is:

FaultMVA=MVA×100Z%=5×1005=100MVAFault \, MVA = \frac{MVA \times 100}{Z\%} = \frac{5 \times 100}{5} = 100 \, MVA

From this, the primary and secondary fault currents can be calculated.

  • Higher impedance → Lower fault current (safer for system protection)

  • Lower impedance → Higher fault current (increases fault level stresses)


Importance of Transformer Impedance

  1. Determines Fault Level

    • A low impedance transformer results in higher fault levels, while high impedance limits fault currents.

  2. Voltage Regulation

    • The percentage impedance indicates the voltage drop under load conditions, affecting system voltage stability.

  3. Parallel Operation

    • For load sharing between multiple transformers, similar impedance values are necessary. Significant mismatch can cause unequal load distribution.


Sequence Impedance (Z₁, Z₂, Z₀)

For balanced 3-phase faults, only the positive sequence impedance (Z₁) is relevant. However, unbalanced faults (e.g., phase-to-earth, phase-to-phase) require symmetrical component analysis.

  • Positive Sequence Impedance (Z₁): Same as negative sequence impedance in transformers.

  • Negative Sequence Impedance (Z₂): Equal to Z₁ in practice.

  • Zero Sequence Impedance (Z₀): Depends on transformer winding connections and earthing.

Key Notes on Zero Sequence Impedance:

  • Zero sequence currents flow only when a path is available (e.g., delta winding or grounded star).

  • Any impedance in the earth return path increases Z₀, thereby limiting earth fault currents.

  • This property is often used in distribution systems to control earth fault levels.


Quick Summary

  • Z% = (Short-circuit test voltage ÷ Rated voltage) × 100

  • High Z% → Low fault current, higher voltage drop, less parallel compatibility

  • Low Z% → High fault current, lower voltage drop, better regulation

  • Critical for fault level calculation, voltage regulation, and transformer parallel operation


Practical Tip: When designing or selecting a transformer, always check its impedance value on the nameplate, as it directly impacts system protection and load sharing performance.



Comments

Popular posts from this blog

A2XWY; A2XFY Cables meaning; XLPE cables advantages over PVC cables

YWY, AYFY, AYY, AYCY, A2XCY Cables Meanings

Cable size and current carrying capacity