No load Test on Transformers; Open Circuit test on Transformers

Open Circuit (No Load) Test on Transformer

The Open Circuit Test, also known as the No Load Test, is performed on a transformer to determine its core losses (iron losses) under no load conditions.




Purpose of the Test

  • To measure core losses (hysteresis and eddy current losses) in the transformer.

  • To calculate parameters of the equivalent circuit (shunt branch).

  • To determine the magnetizing current.




Why High Voltage Side is Kept Open?

  • In the open-circuit test, one winding of the transformer is left open.

  • The high-voltage (HV) winding is kept open, and the test is performed from the low-voltage (LV) side.

  • This is because:

    • At rated HV, the current is very small (hard to measure accurately).

    • Instruments required for HV would need higher insulation and safety.

    • So, LV side is used for practical measurement.


Test Connections

  • A Voltmeter, Ammeter, and Wattmeter are connected on the LV side.

  • The HV side is left open.

  • Supply is applied to the LV side using a Variac (to gradually increase voltage).

  • The applied voltage is increased until it reaches the rated LV value.

📌 Circuit Diagram (Conceptual)

      LV Side (Test side)                   HV Side (Open)
   ┌─────────────┐
   │             │
   │   Ammeter   │
   │             │
   └─────┬───────┘
         │
      ┌──┴───┐
      │      │   Voltmeter
   Variac    ├────────────┐
      │      │            │
      └──────┘        Transformer LV winding → HV winding open
         │
   Wattmeter

Readings Taken

  • Voltmeter (Vo): Applied voltage (rated LV value).

  • Ammeter (Io): No-load current (very small, < 5% of rated current).

  • Wattmeter (Po): Power input to transformer under no load = Core loss.


Theory

Since:

  • Secondary is open, → No load current flows in HV side.

  • Copper losses (I²R) in LV side are negligible (Io is very small).

  • Therefore, Wattmeter reading ≈ Core losses.

The input power is expressed as:

Po=Vo2/RmP_o = V_o^2 / R_m

Where:

  • PoP_o = Core loss (from Wattmeter)

  • VoV_o = Applied LV rated voltage

  • RmR_m = Shunt resistance of equivalent circuit


Conclusion

  • The Open Circuit Test gives the core losses of the transformer at rated voltage.

  • It also helps to calculate the magnetizing branch parameters (Rm & Xm) of the equivalent circuit.


👉 Related: Short Circuit Test on Transformer



Comments

Popular posts from this blog

A2XWY; A2XFY Cables meaning; XLPE cables advantages over PVC cables

YWY, AYFY, AYY, AYCY, A2XCY Cables Meanings

Cable size and current carrying capacity