Search This Blog

Saturday, September 16, 2017

National Electricity code,NFPA 70 for Examination, Identification, Installation, and Use of electrical Equipment

NFPA 70 (NEC) – Examination, Identification, Installation, and Use of Electrical Equipment

The National Electrical Code (NEC), NFPA 70, establishes mandatory rules to ensure the safe installation and use of electrical equipment. Below is a simplified breakdown of key requirements:


1. Examination of Electrical Equipment

Before approving equipment for installation, the following must be checked:

  • Suitability for purpose/environment/application (labeling, instructions, or listing).

  • Mechanical strength and durability of enclosures.

  • Adequate space for wire bending and connections.

  • Electrical insulation integrity.

  • Heating and arcing effects under normal and abnormal conditions.

  • Classification by type, voltage, and current rating.

  • Other safety factors relevant to user protection.




2. Installation and Use

  • Equipment must be installed as per listing or labeling instructions.

  • Voltage rating of equipment ≥ circuit’s nominal voltage.

  • Conductor material: Copper is standard unless otherwise stated.

  • Conductor sizes: Expressed in AWG or circular mils.

  • Wiring integrity: Free from shorts and ground faults.

  • Wiring methods: Only NEC-approved methods are acceptable.

  • Interrupting rating: Equipment must withstand fault currents safely.


3. Mounting and Cooling

  • Equipment must be firmly mounted, not on wooden plugs.

  • Natural ventilation must not be blocked; adequate clearance for heat dissipation is required.


4. Electrical Connections

  • Mixing of dissimilar metals (Cu-Al, Cu-Cu clad Al, etc.) must be avoided.

  • Fluxes and compounds must not harm conductors.

  • Terminals should be connected via pressure connectors, solder lugs, or hydraulic punching.

  • Splices must be mechanically secure before soldering and properly insulated.

  • Temperature limits: Conductor temperature rating must not exceed the lowest-rated component.


5. Equipment Provisions

  • Circuits ≤100 A: Only 60°C rated conductors unless listed for higher.

  • Circuits >100 A: 75°C rated conductors or higher with proper listing.

  • Separate connectors must not exceed their temperature rating.


6. Additional NEC Requirements

  • High-leg marking: Orange marking for high-leg in 4-wire delta systems.

  • Arc-flash hazard warning: Labels required on switchboards, panelboards, MCCs, etc.

  • Arcing parts: Must be enclosed/isolated from combustibles.

  • Markings: Manufacturer’s name, voltage, current ratings, etc. must be durable.

  • Disconnect means: Clearly marked for identification.

  • Series combination ratings: Must be visibly marked (engineered/tested).

  • Current transformers: Unused CTs must be short-circuited.

  • Available fault current: Must be field-marked and updated after modifications.

What You Can Do

  • Visit NFPA's Website: You can access the official NFPA 70 Standard (current edition and any Tentative Interim Amendments or errata) at the NFPA Document Information page. Simply go to www.nfpa.org/docinfo, search for NFPA 70, and download or view the figures as part of the standard. (Revize, NFPA)
  • Refer to the Official Handbook: The National Electrical Code® Handbook contains expanded commentary and annotated explanations with accompanying figures and diagrams.
  • Purchase or Access Through Subscriptions: Many institutions, organizations, or professionals subscribe to NFPA codes for legal compliance, training, and technical reference.

Quick Guide to Common Figure Types in NFPA 70

Figure Type

Typical Use

Enclosure and Equipment Layout

Demonstrates spacing, clearances, and mounting guidelines consistent with 110.26 and other requirements

Wiring Methods & Raceway Fill

Illustrates allowed conduit/busway fill percentages and conductor routing

Bonding & Grounding Diagrams

Shows proper connections in service equipment, sub-panels, and equipment grounding systems

Disconnecting Means Layout

Clarifies marking and visibility requirements per 100, 110, and disconnect provisions

Arc-Flash Hazard Marking

Visual placement for warning labels on panels and switchgear


Summary

  • NFPA 70 includes detailed figures accompanying various installation and safety requirements—but these diagrams are not freely accessible online.
  • You should obtain the actual standard or handbook through NFPA to view these figures.
  • NFPA’s official site is the most reliable avenue for accessing up-to-date figures, context, and explanatory material. (Revize, NFPA)

 


In short: NFPA 70 ensures electrical equipment is properly tested, mounted, cooled, connected, marked, and protected against hazards like short circuits, arc flash, overheating, and mechanical failures.



No comments:

Post a Comment

Note: Only a member of this blog may post a comment.