Electrical Wiring Estimate for a 100 Gaj House

 For a 100 gaj house (approximately 900 sq. ft. or 83.6 m²),generally concealed copper wiring system using FRLS (Flame Retardant Low Smoke) insulated wires, separate circuits for air conditioners and heavy appliances, and an appropriately rated distribution board (DB) with modern electrical protection to be used.

The following is a preliminary quantity and cost estimate for a typical 2–3 BHK house with a kitchen, bathrooms, living room, bedrooms, and a small utility area.

Important: The wire sizes and quantities below are planning estimates. Final sizing depends on actual connected load, circuit length, installation method, voltage drop, ambient temperature, grouping, and the applicable electrical standards.



1. Assumptions for the Estimate

Particular

Assumption

Covered area

100 gaj (900 sq. ft.)

House configuration

2–3 BHK, single floor

Wiring method

Concealed conduit wiring

Conductor

99.9% copper, FRLS insulated

Supply

230 V single-phase, subject to sanctioned load

Air conditioners

3 split ACs

Lighting points

25

Ceiling fans

5

6A socket points

15

16A power points

8

Geysers

2

Kitchen heavy appliances

Microwave, refrigerator, washing machine and other appliances as applicable

Distribution board

Modular DB with MCBs, RCCB/RCBO protection and surge protection as appropriate

The estimate assumes that the house is already constructed or being fitted out and that the work includes wiring, conduits, accessories, and distribution-board installation. Major civil repairs, plastering, painting and premium decorative fixtures are excluded unless specified.

2. Recommended Wire Sizes for Different Appliances

Wire size should be selected according to the actual load, current-carrying capacity, voltage drop, installation conditions and protective-device rating. India's relevant reference standard is IS 732:2019 — Code of Practice for Electrical Wiring Installations. BIS

Sr. No.

Circuit / Appliance

Recommended copper wire size for preliminary planning

Suggested circuit protection*

1

LED lights

1.5 mm²

6A or 10A MCB

2

Ceiling fans

1.5 mm²

6A or 10A MCB

3

General 6A sockets

2.5 mm²

10A or 16A MCB

4

Refrigerator

2.5 mm²

Dedicated 16A circuit where appropriate

5

Television and computer

2.5 mm²

10A or 16A MCB

6

Washing machine

2.5 or 4 mm²

Dedicated circuit; rating based on appliance

7

Microwave oven

2.5 or 4 mm²

Dedicated circuit; rating based on appliance

8

1-ton split AC

2.5 or 4 mm²

Dedicated 16A/20A circuit, subject to load

9

1.5-ton split AC

4 mm² as a planning provision

Dedicated circuit; typically 16A/20A subject to manufacturer requirements

10

2-ton split AC

4 or 6 mm²

Dedicated circuit, sized by calculation

11

2 kW geyser

2.5 or 4 mm²

Dedicated circuit; typically 16A, subject to design

12

3 kW geyser

4 mm²

Dedicated circuit; protective rating based on design

13

Kitchen heavy appliances

2.5 or 4 mm²

Separate circuits according to appliance loads

14

DB to room sub-distribution board, if provided

6 or 10 mm²

Based on aggregate demand and route

15

Main incoming supply

10 or 16 mm² may be considered

Based on sanctioned load, demand and supply arrangement

*These are indicative selections, not final design ratings. The electrician must calculate the actual current, verify the wire's derated ampacity, coordinate MCBs with the cable and account for voltage drop and fault protection.

Buy House Wiring Kit by clicking at Image or Link



Special recommendations for AC wiring

For a typical house with three split ACs:

  • Bedroom 1: Independent AC circuit.
  • Bedroom 2: Independent AC circuit.
  • Bedroom 3 / drawing room: Independent AC circuit.
  • Provide a suitable isolator near each outdoor unit as required by the manufacturer's instructions and applicable standards.
  • Do not connect multiple ACs to one general-purpose socket circuit.
  • Keep an adequate earth conductor with each circuit.

Engineering recommendation: Do not select AC wire size solely on the basis of tonnage. Check the nameplate current, rated input, maximum operating current, cable length, installation conditions and manufacturer's instructions before finalising the wire size.


3. Detailed Electrical Wiring Quantity Estimate

The following quantities are budgetary estimates for a 900 sq. ft. house. Actual quantities can vary significantly depending on the room layout, location of the DB, number of switchboards and routing of concealed conduits.

A. Copper wire requirement

For estimating purposes, assume standard 90-metre wire coils. Quantities below represent the approximate combined length of conductors in all required colours, including phase, neutral and earth where applicable.

Sr. No.

Wire size

Estimated total length

Equivalent 90 m coils

Main application

1

1.5 mm² copper FRLS

900 m

10 coils

Lighting and fans

2

2.5 mm² copper FRLS

900 m

10 coils

General sockets and selected appliance circuits

3

4 mm² copper FRLS

360 m

4 coils

ACs, geysers and heavy appliances

4

6 mm² copper FRLS

180 m

2 coils

Selected higher-load circuits/submain

5

10 mm² copper FRLS

90 m

1 coil

Main/submain wiring, if required

6

4 mm² green/yellow earth conductor

90 m

1 coil

Supplementary earthing and circuit earths, as designed

Total

2,520 m

28 coils

Preliminary provision

Important quantity note: The 2,520-metre total is the sum of the conductor lengths, not the length of the physical cable route. For example, a 20-metre route may require separate phase, neutral and earth conductors. Earth conductors should be included in the actual circuit take-off, and the additional 4 mm² earth provision above should not be treated as a substitute for them.

The final purchase should be based on a room-wise wiring layout and an actual site measurement. Do not order all coils solely on the basis of this preliminary table.

B. Conduit, boxes and accessories

Sr. No.

Material

Estimated quantity

Unit

1

Heavy-duty PVC concealed conduit, 20 mm

250

Metres

2

Heavy-duty PVC concealed conduit, 25 mm

75

Metres

3

PVC junction boxes

25

Nos.

4

Modular switch boxes of various sizes

20

Nos.

5

Modular switchboards and plates

20

Nos.

6

6A switches

40

Nos.

7

16A switches and socket outlets

8 sets

Sets

8

6A socket outlets

15

Nos.

9

Fan regulators

5

Nos.

10

Ceiling fan hook boxes

5

Nos.

11

Light/fan outlet boxes

25

Nos.

12

AC isolators/suitable local disconnectors

3

Nos.

13

Conduit bends, couplers, saddles and accessories

1

Lot

14

Insulation tape, connectors, screws and consumables

1

Lot

These quantities assume concealed conduit installation. If the house has already been plastered, chasing, plaster repair and repainting may add substantially to the cost.


4. Distribution Board (DB) and Protection System

For a house with three ACs, two geysers, kitchen appliances and normal lighting loads, a properly designed distribution board is essential.

Recommended DB specification

Sr. No.

Component

Preliminary specification

Quantity

1

Main distribution board

18-way or 24-way modular DB, subject to circuit schedule

1

2

Main incomer

DP main isolator, typically 40A/63A as determined by load

1

3

RCCB

30 mA residual-current protection, with suitable type and rating

As designed

4

RCBOs

Individual overcurrent and residual-current protection for selected circuits

As designed

5

MCBs

Suitable ratings and breaking capacity for each circuit

As required

6

Type 2 SPD

Surge protection device, if required by the installation's risk assessment and design

1 set

7

Neutral and earth bars

Correctly rated and arranged

1 set

8

Earthing system

Suitable electrodes/connections and protective earth conductors

As required

Important: An 18-way or 24-way DB is a starting point, not a confirmed requirement. Finalise its size after preparing the circuit schedule. The main MCB rating must not be selected merely because the house has three ACs.

A 30 mA RCCB/RCBO provides additional protection against electric shock; it does not replace earthing or overcurrent protection. Neutral conductors must be arranged correctly, and circuits protected by separate RCBOs must not have their neutrals improperly interconnected.

For Indian installations, refer to the applicable requirements of the Bureau of Indian Standards (IS 732:2019) and the Central Electricity Authority's safety regulations.

5. Electrical Load Estimate

The connected load of a typical 100 gaj house may be estimated as follows. These are illustrative loads, not measured appliance ratings.

Sr. No.

Appliance

Quantity

Assumed load per unit

Total connected load

1

LED lights

25

12 W

0.30 kW

2

Ceiling fans

5

70 W

0.35 kW

3

Television

2

100 W

0.20 kW

4

Refrigerator

1

250 W

0.25 kW

5

Washing machine

1

1,000 W

1.00 kW

6

Microwave oven

1

1,500 W

1.50 kW

7

Geysers

2

2,000 W

4.00 kW

8

Split ACs

3

1,500 W

4.50 kW

9

Kitchen appliances and other sockets

—

Allowance

2.00 kW

Total illustrative connected load

14.10 kW

The actual connected load may be higher or lower depending on the appliance ratings.

What does this mean for the electrical supply?

At 230 V, a 14.1 kW connected load would draw approximately 61.3 A if all the loads operated simultaneously at unity power factor. Actual current depends on the appliance characteristics.

For this reason:

  • The sanctioned load and supply arrangement must be verified with the electricity distribution company.
  • A three-phase supply may be appropriate if required by the calculated demand and applicable supply conditions.
  • If three-phase supply is provided, the circuits must be distributed across phases to balance the load.
  • The main cable and protection devices must be selected using a proper demand and fault-current calculation.

Do not assume that a 40A single-phase supply is sufficient merely because the property is 100 gaj.


6. Approximate Electrical Wiring Cost Estimate

The following is an indicative budgeting estimate for Delhi/NCR. Prices are approximate allowances, not verified quotations from electrical contractors or manufacturers.

Sr. No.

Description

Estimated amount

1

Copper FRLS wires of various sizes

₹65,000–₹90,000

2

PVC conduits, junction boxes and accessories

₹12,000–₹20,000

3

Modular switches, sockets and switch plates

₹20,000–₹40,000

4

Distribution board, MCBs, RCCB/RCBOs, isolators and SPD

₹15,000–₹30,000

5

Earthing system and protective earth wiring

₹8,000–₹18,000

6

Fan boxes, connectors, lugs and miscellaneous accessories

₹5,000–₹10,000

7

Electrical installation and wiring labour

₹35,000–₹55,000

8

Chasing, conduit laying and basic plaster repairs

₹10,000–₹20,000

Estimated total

₹1,70,000–₹2,83,000

Recommended budget

For preliminary financial planning, keep a budget of approximately ₹2.25 lakh for the complete basic electrical wiring installation.

The estimate assumes ordinary modular accessories and standard-quality materials. Premium switchgear, additional AC circuits, concealed ceiling work, extensive civil repairs, decorative lighting and other special requirements may increase the cost.

Items not included

The above estimate excludes:

  • Purchase of air conditioners, geysers, fans and other appliances.
  • Decorative lights, chandeliers and premium LED fixtures.
  • Inverter, battery and solar installation.
  • Smart-home automation.
  • Electrical meter and utility connection charges.
  • Major plastering, painting and structural repairs.
  • Additional floors, external landscaping or garden lighting.
  • GST where applicable to the contractor's quotation.

Before approving a contractor's estimate, obtain a detailed bill of quantities with make, model, wire length, accessories, labour rates and GST clearly identified.


7. Recommended Circuit Schedule

For better reliability and easier fault finding, avoid putting all appliances on a few common circuits.

Circuit

Description

Wiring provision

C1

Living room and bedroom lights

1.5 mm² copper

C2

Remaining lights and fans

1.5 mm² copper

C3

General sockets in bedrooms

2.5 mm² copper

C4

Living room and TV sockets

2.5 mm² copper

C5

Kitchen general sockets

2.5 mm² copper, subject to load

C6

Refrigerator

Dedicated circuit, where appropriate

C7

Washing machine

Dedicated circuit

C8

Microwave and heavy kitchen appliances

Separate circuits as required

C9

AC in bedroom 1

Dedicated circuit

C10

AC in bedroom 2

Dedicated circuit

C11

AC in bedroom 3/living room

Dedicated circuit

C12

Geyser in bathroom 1

Dedicated circuit

C13

Geyser in bathroom 2

Dedicated circuit

C14

Spare circuit

Provision for future requirements

The final circuit arrangement may be revised to suit the room layout, connected load and the applicable installation standards.

8. Engineering Checks Before Handover

Before the installation is energised, ensure that the contractor carries out and documents the following checks:

  1. Insulation resistance test: Verify insulation integrity of the installed circuits.
  2. Continuity test: Verify continuity of protective conductors and other required conductors.
  3. Polarity test: Confirm correct phase and neutral connections at outlets and switches.
  4. Earthing verification: Check protective earthing continuity and the earthing system's effectiveness.
  5. RCCB/RCBO testing: Verify operation using suitable test equipment.
  6. Load and voltage-drop verification: Confirm that conductors and protective devices are suitable for actual loads and circuit lengths.
  7. DB labelling: Label each circuit clearly for future maintenance.
  8. As-built drawing: Obtain the final wiring layout and circuit schedule from the contractor.

The applicable verification requirements should be followed under IS 732 and the relevant electrical safety regulations. BIS


9. Disclaimer

This estimate is prepared for preliminary budgeting and planning purposes only. The quantities, wire sizes, circuit arrangements, equipment ratings and costs are indicative and are based on assumed requirements for a typical 100 gaj residential house.

The final design and estimate must be prepared or verified by a competent electrical engineer after inspecting the property, confirming the actual floor plan, appliance nameplate ratings, sanctioned load, supply type, cable routing, installation conditions and applicable statutory requirements.

All electrical work must be carried out by an appropriately licensed electrical contractor, with suitable testing and verification before energisation. Wire sizes and protective-device ratings must not be finalised solely on the basis of this estimate. The actual cost will depend on prevailing material prices, brands, site conditions, labour rates, taxes and the final scope of work.

This document is not a substitute for a site-specific electrical design, approved drawings or a certified electrical safety inspection.

 