For Tan-delta, Loss angle test visit link:-
http://electrialstandards.blogspot.com/2015/10/tan-delta-test-loss-angle-test.html
Below are the technical specifications of Oil type 990 KVA transformer :-
For Transformer Oil Filteration process visit link:-
http://electrialstandards.blogspot.in/2015/10/transformer-oil-filtration-process.html
Tank
|
Type
Tested Design
|
|
Design
|
a)
Completely sealed type with corrugated fins and with/without conservator tank
as per site requirements
b) Completely oil filled or N2 cushion at
top filled with positive pressure. N2 shall be technical grade in accordance
with IS:1747
c) With bolted / welded cover
|
|
Plate
/ Corrugated fin / tank features
|
a)
Adequate for meeting mechanical & electrical withstand requirements, as
per applicable standard.
b)
The tank and its sealing (gaskets, o-rings, etc.) shall be of adequate
strength to withstand positive and negative pressures built-up inside the
tank while the transformer is in operation. The maximum pressure generated
inside the tank should not exceed 40kPa, positive or negative.
c)
Corrugated fins shall be built up of CRCA sheets of minimum 1.2mm thick.
d)
The corrugated tank wall shall ensure sufficient cooling of the transformer and
compensate for the changes in the oil volume during operation.
e) The transformer shall be capable of
giving continuous rated output, without exceeding the specified temperature
rise.
f)
Internal clearance of tank shall be such that, it shall facilitate easy
lifting of core with coils from the tank and HV & LV bushings mounted on
Top cover.
g) All joints of tank and fittings shall be
oil tight. The tank design shall be such that the core and windings can be
lifted freely with cover. The tank plate shall be of such strength that the
complete transformers when filled with oil may be lifted bodily by means of
lifting lugs.
h)
Tanks with corrugations & without conservator shall be tested for leakage
at a pressure as per the applicable standard.
|
|
Material
of Construction
|
Mild
steel plate with low carbon
|
|
Plate
Thickness
|
To
meet the requirements of pressure and vacuum type tests as per CBIP manual
|
|
Welding
features
|
a)
All seams and joints shall be double welded
b)
All welding shall be stress relieved for sheet thickness greater than 35 mm
c)
All pipes, stiffeners, welded to the tank shall be welded externally
d) All corrugated fins or expansion bellows
provided shall be double welded.
|
|
Tank
features
|
a)
Bottom with stiffeners & adequate space for collection of sediments
b)
No external pocket in which water can lodge
c)
Tank bottom with welded skid base
d)
Strength to prevent permanent deformation during lifting, jacking,
transportation with oil filled.
e) Minimum
disconnection of pipe work and accessories for cover lifting
f) Tank to be designed for oil filling under
vacuum g) Tank cover fitted with lifting lug
|
Winding
|
||
Material
|
Electrolytic
Copper
|
|
Maximum
Current Density allowed
|
Maximum
3 amp / sqmm
|
|
Winding
Insulating material
|
Class
A, non catalytic, inert to transformer oil, free from compounds liable to ooze
out, shrink or collapse.
|
|
Winding
Insulation
|
Uniform
|
|
Design
features
|
a)
Stacks of winding to receive adequate shrinkage treatment.
b)
Connections braced to withstand shock during transport, switching, short
circuit, or other transients.
c) Minimum out of balance force in the
winding at all voltage ratios.
d)
Conductor width on edge exceeding six times its thickness.
e)
Transposed at sufficient intervals.
f) Coil assembly shall be suitably supported
between adjacent sections by insulating spacers + barriers.
g)
Winding leads rigidly supported, using guide tubes if practicable.
h) Winding structure & insulation not to
obstruct free flow of oil through ducts.
i)
Delta connection shall be done using Flexible cable.
|
Bushings
and Terminations
|
||
Type
of HV side bushing
|
Epoxy
cast bushing, 630 Amp, interface type ‘C’ as per EN50180 and EN50181.
|
|
Type
of LV side bushing
|
Indoor,
Epoxy resin cast, 1kv voltage class and creepage 31mm/KV
|
|
Essential
provision for LV side line bushing
|
It
shall be complete with copper palm suitable for tinned copper busbar of size
100x12 mm
|
|
Essential
provision for LV side neutral bushing
|
In
case of neutral bushing the stem and bus bar palm shall be integral without
bolted, threaded, brazed joints. Bus bar size shall be 100x12 mm
|
|
Arcing
Horn
|
As
per site requirements
|
|
Termination on HV side bushing
|
Cable
connection by screened separable connector kit.
|
|
Termination of LV side bushing
|
Bus
bar connections
|
|
Minimum creepage distance of all bushings and
support insulators.
|
31mm/kv
|
|
Protected creepage distance
|
At
least 50 % of total creepage distance
|
|
Continuous Current rating
|
Minimum
20 % higher than the current corresponding to the minimum tap of the
transformer
|
|
Rated thermal short time current
|
26.3kA
for 3 sec
|
|
Bushing terminal lugs in oil and air
|
Tinned
copper
|
Current Transformers
|
All
three phases and neutral on LV side
|
Maintenance requirements
|
Replacement
should be possible by removing fixing nut of mounting plate without
disturbing LT bushing
|
Accuracy Class
|
5P10
|
Burden
|
5VA
|
Type
|
Resin
Cast Ring type suitable for outdoor use
|
CT ratio
|
990KVA -1500/5 Amp
|
For Parallel Operation of Transformers Visit link:-
http://electrialstandards.blogspot.com/2015/10/parallel-operation-of-transformers.html
Core
|
|
Grade
|
High
grade , non- ageing, low loss, high permeability, grain oriented, cold rolled
silicon steel lamination
|
Core
Design Features
|
a)
Magnetic circuit designed to avoid short circuit paths within core or to the
earthed clamping structures.
b)
Magnetic circuit shall not produce flux components at right angles to the
plane of lamination to avoid local heating.
c) Least possible air gap and rigid clamping
for minimum core loss and noise generation.
d)
Adequately braced to withstand bolted faults on secondary terminals without
mechanical damage and damage/ displacement during transportation and
positioning.
e) Percentage harmonic potential with the
maximum flux density under any condition limited to avoid capacitor
overloading in the system.
f) All steel sections used for supporting
the core shall be thoroughly sand blasted after cutting, drilling, welding.
g)
Provision of lifting lugs for core coil assembly.
h)
Supporting framework designed not to obstruct complete drainage of oil from
transformer
|
http://electrialstandards.blogspot.com/2015/10/parallel-operation-of-transformers.html
For Tan-delta, Loss angle test visit link:-
http://electrialstandards.blogspot.com/2015/10/tan-delta-test-loss-angle-test.html

