66KV to 132KV Cables Tests requirement
Here’s a detailed breakdown of the required tests for 66
kV and 132 kV XLPE cables per IS 7098 (Part 3)
(covering 66 kV up to and including 220 kV), with reference to IS
60840 equivalents where applicable:
IS 7098 (Part 3): Tests for 66 kV & 132 kV XLPE Cables
Based on the BIS Product Manual for IS 7098 (Pt 3),
the following tests are specified—applicable to each completed length of cable
and per manufacturing batch/consignment (BIS):
π Test Checklist for 66 kV & 132 kV XLPE
Power Cables
Standards Referenced: IS 7098 (Part 3), IS 60840 / IEC
60840
1. Routine Tests (Every Delivered Cable Length)
Test |
Sequence |
Acceptance
Criteria |
Conductor resistance |
Pre-insulation |
≤ values specified in IS 7098 (as per cross-section &
temp. corrected to 20 °C) |
Partial Discharge (PD) test |
After manufacturing, before HV |
PD ≤ 5 pC at 1.5 × U₀ (U₀ = phase-to-earth voltage) |
High Voltage (HV) test, 1
min |
After PD test |
Withstand: 160 kV (66 kV class), 275 kV (132 kV class), no
breakdown |
Conductor & sheath
inspection |
Visual & dimensional |
Within tolerance of IS 7098 Pt-3 |
2. Sample Tests (One Length per Batch / Consignment)
Test |
Sequence |
Acceptance
Criteria |
Check of cable dimensions |
Pre-electrical |
Within IS 7098 tolerances |
Tensile strength &
elongation (insulation/sheath) |
Before ageing |
≥ 12.5 N/mm² tensile; ≥ 200% elongation |
Hot set test (XLPE
insulation) |
200 °C, 20 N/cm² |
Elongation ≤ 175%, permanent set ≤ 15% |
Shrinkage test (insulation) |
Post heating |
≤ 4% |
Water penetration (if
required) |
Longitudinal / radial |
No water ingress in defined period |
Dielectric power factor
& capacitance |
Ambient & elevated temp. |
Tan Ξ΄ ≤ 0.001 at U₀, stable trend |
Bending test + PD |
Mechanical + electrical |
No cracks; PD ≤ 5 pC |
Flammability (PVC sheathed
cables) |
Vertical flame test |
Self-extinguish within 60 s |
3. Type Tests (Once per Design / Before Approval)
Test |
Sequence |
Acceptance
Criteria |
Lightning impulse withstand |
After routine HV test |
Withstand: 350–380 kV (66 kV); 650 kV (132 kV), no
flashover/breakdown |
Load cycle test (with PD
monitoring) |
Repeated heating/cooling cycles |
PD ≤ 5 pC throughout; no failure |
Long-term thermal ageing
(insulation/sheath) |
Accelerated ageing |
Retention ≥ 80% tensile & elongation |
Resistance of
semi-conducting layers |
As per IS 7098 |
≤ specified Ξ©·m resistivity |
Short-circuit withstand
test |
Calculated or tested |
Cable survives specified kA²s duty without damage |
Impulse + Power frequency
withstand of accessories (joints/terminations) |
After installation simulation |
No breakdown; PD ≤ 5 pC |
Notes
·
Sequence: Mechanical/physical
tests → PD → 1-min HV → Impulse withstand (for type) → Load cycle.
·
Acceptance: Any failure in
routine test → reject length. Any failure in sample/type test → corrective
action + retest.
·
Reference Um values:
o
66 kV cables → Um = 72.5 kV
o
132 kV cables → Um = 145 kV
✅ This checklist is structured for FAT /
vendor QA:
·
Routine = each cable length
·
Sample = one per
batch/consignment
·
Type = once per design
Do you want me to also format this into a professional table layout
(Word/PDF-style) with company logo placeholders so you can use it
directly in vendor FAT documentation?
Summary Table: IS 7098 (Pt 3) Key Tests for 66 kV & 132 kV XLPE Cables
Test Category |
IS 7098 Pt 3 Requirements
(Frequency) |
Conductor & Material Properties |
Annealing, resistance, screening, insulation, armouring
(each length or batch) |
Sheath & Insulation Physical Tests |
Thickness, tensile, hot set, shrinkage, aging (length-wise
or batch-wise) |
Semi-Conducting Layer Resistivity |
Monthly sampling |
Electrical & Dielectric Tests |
Dielectric power factor, capacitance, load cycle, impulse,
PD, HV withstand (daily to fortnightly) |
Thermal & Environmental Durability |
Thermal ageing, water tightness, bending + PD,
flammability (monthly to quarterly) |
Optional Tests |
Cold impact, spark voltage on outer sheath (as agreed) |
In Summary
·
66 kV and 132 kV XLPE
cables under IS 7098 (Part 3) must
undergo a comprehensive suite of type, routine, and
acceptance tests, covering physical, mechanical, electrical,
and environmental performance aspects.
·
Many of these parallel the IEC
60840 standard’s requirements for high-voltage extruded cable
systems (30–150 kV), ensuring a globally aligned framework.
·
Frequency
varies: some tests are mandatory per length, others per batch/consignment,
and system-level electrical tests (e.g., impulse, load cycling, PD) follow a
stricter routine (daily, fortnightly, monthly, or quarterly).
Nice — here are the standard numeric test voltages
you asked for (power-frequency 1-minute and lightning-impulse) that are
normally applied to 66 kV and 132
kV XLPE cable systems. I pulled these from IEC 60840 / allied
technical specs and BIS product material so you can use them directly in test
procedures or technical specifications.
Quick note: in standards/workspecs the cable rated/system voltages
are often expressed as the highest system voltage (Um). In practice 66 kV class
equipment is normally treated as Um = 72.5 kV
and 132 kV as Um = 145 kV; test
voltages in IEC/IS are defined against those class voltages. The tables below
therefore use the commonly adopted Um equivalents.
Recommended test voltages (typical values used in IEC 60840 / practice)
Cable class
(nominal) |
Common Um used in
standards |
Power-frequency
withstand (r.m.s.) — 1 min |
Lightning impulse
withstand (1.2/50 Β΅s) — peak |
66 kV |
72.5 kV |
~160 kV (rms) — 1 min. (Tianan
Group) |
~350 – 380 kV (peak)
(commonly quoted 350–380 kV for 72.5 kV class). (Tianan
Group, Hitachi
Energy) |
132 kV |
145 kV |
~275 kV (rms) — 1 min (often
specified as 275 kV). (Hitachi
Energy, Bharat Heavy Electricals
Limited) |
~650 kV (peak) (typical
lightning impulse level for 145 kV class). (Hitachi
Energy, Bharat Heavy Electricals
Limited) |
Additional clarifications & practical points
·
Duration &
waveforms: the power-frequency test is normally applied for 1
minute (r.m.s. sinusoidal). The lightning test is standard 1.2/50
Β΅s impulse (peak) as per IEC conventions.
·
Where these appear in
standards: IEC-60840 contains the normative
relationships/tables that give test voltages related to rated voltages (see
clause on “relationship of test voltages to rated voltages” and Table(s) of
test voltages). IS-7098 (Pt-3) follows the same framework for 66–220 kV XLPE
cables (BIS Product Manual references). (BIS)
·
Range / rounding:
some documents quote slightly different numbers depending on whether they use
the nominal rated voltage (66/132 kV) or the standard Um value (72.5/145 kV) —
and whether they round to manufacturer/utility practice. That’s why you see
small spreads (e.g., 350 vs 380 kV). For procurement/test sheets use the exact
numeric values called out by the purchaser/utility (or the specific
clause/table in IEC 60840 / IS 7098 that applies). (BIS)
·
Accessories / joints /
terminations: the impulse + power-frequency sequence and
specific values for joints/terminations are covered in IEC-60840 Annexes/tables
(H, G). Those accessory values can differ from cable-only values — check the
relevant table when testing accessories.
MRS Agencies is a TOP Copper Bonded Chemical Earthing Electrode Manufacturers in India. Our is a professionally-managed organization that guarantees the high quality of our product variety is maintained thoroughly. We can also customize these Pure Copper Earthing Electrode, Chemical Earthing/ Gel Earthing Electrode, Chemical Pipe Earthing Electrode, Lightning Arrester, products as per requirements detailed down by the clients.
ReplyDelete