Current
transformers are used to convert alternating current of higher value to lower
value depending upon the requirement. Current Transformers has many
applications in electrical systems.
Current
Transformers usually have two types of designs:-
1. Window type
2. Ring Type
There
are generally two type of applications where Current Transformers are used:-
1. Measurement
Type Current Transformers
2. Protection
Type current Transformers
Measurement
type CT’s design requires the inclusion of core and winding which will which
will when connected to its rated burden; perform within the limits of error as
indicated by the standard’s specification. It is an advantage for a measurement
type transformer to saturate above this range, which provides a protection
against damage to instruments by limiting the secondary current when surge
currents or faults appear in the primary circuit.
There
are following Specification of current Transformers:-
Rated
Transformation Ratio:-
It is the ratio of rated primary current to rated secondary
current
Rated
primary current:
It is primary current which is to be Transformed to
secondary current as per requirement. Usually rated primary current is the
current flowing in system whose value to be converted to as per requirement. CT
should be selected according to this current.
Rated
secondary current:
This
is the secondary current of Transformer. This current is obtained after
Transformation by CT. Typical values of secondary current are 5 A and 1A.
Rated
burden:
This
is expressed in VA and is an apparent power of the secondary circuit of CT. It
is specified on CT’s as per rated secondary current of CT’s at 0.8 Power
factor.
Accuracy
class:
Accuracy class will depend upon type of
application where CT is used. In case of metering accuracy class is 0.2, 0.5, 0.1,
1, 3 or 5. It means that the errors have
to be within the limits specified in the standards for that particular accuracy
class. The accuracy class of measuring CT is 0.2 it means the error limit will
be of 0.2%. This means that if we try to measure 100 A with a 0.2 class CT, the
measured value may be either 100.2 or 99.8 A.
For
protection type CT’s the CT s should
pass both the ratio and phase errors at the specified accuracy class, usually
5P or 10P where 5 stands for 5% and 10 stands for 10% and P stands for
Protection.
Current error (ratio error):
This error is
introduced into measurement by CT generally due to Transformation error. This
error is difference between primary current to be measured and Secondary
current multiplied by Transformation ratio.
This is
expressed by formula as below
Current error,
percent =[ (K X.Is)- (Ip)] x 100 / Ip
Where, K= rated
transformation ratio
Ip= actual
primary current
Is= actual secondary current
Accuracy
limit factor:
This
is error value of primary current upto which the CT complies with composite
error requirements.
Phase
displacement:
Phase
displacement as clear from its name is difference in phase between the primary
and secondary current vectors.
The phase displacement is said to be positive
when the secondary current vector leads the primary current vector. It is
usually express in minutes.
Composite error:-
This
error is the subsequent limitation of the harmonic content of the secondary
current which is necessary for the correct operation of certain types of relays.
Diameter of CT:-
Bore diameter of the CT shall not
be less than 40 mm. Ring type CTs shall have suitable clamp to fix the CT to
panel Board.
Highest Withstand Voltage: -
This is highest voltage which is needed to withstand
by CT without getting faulty. This doesn’t include the voltage variations in
case of fault conditions.
General Technical Specifications of Current
Transformers
Standards applicability: -
IS/IEC 60044-1 (2003): Instrument
Transformers, Part 1: Current Transformers
BS 3938:1973 :Specification for
current transformers
Insulation class: -
E
(120°C max)
Test voltage: -
For
Ring (Window) type CT : 4KV 50 Hz for 1 min
For
Wound type CT : 3KV 50 Hz for 1 min
Operating frequency: -
50Hz
Rated primary rating: -
1A
to 7500A
Rated secondary output: -
5A
standard (1A on request)
Rated burden: -
1,
1.25, 1.5, 2.5, 3.75, 5, 7.5, 10, 12.5, 15, 20, 30, 45, 60, 100 VA
Class of accuracy: -
0.2,
0.2S for laboratory and power measurement
0.5,
0.5S for accurate measuring, kWh
1
for general measurement
3
for indicating instruments
Ambient temperature:
- -20°C…+45°C
Storage temperature: -
-50°C…+80°C
Thermal short circuit current (Ith):-
40xIn
for Wound type CT and
60xIn
for Bus Bar type CT.
Dynamic short circuit current (Idyn):-
2.5xIth
Instrument security factor (FS): -
2.5,
5, 10
Limits of current error and phase displacements for measuring current transformers
(Classes from 0.1 to 1)
Limits of current error and phase displacements for measuring current transformers
(For special applications)
Limits of current error and phase displacements for measuring current transformers
(Classes 3 and 5)
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.