In electrical Systems we have seen Single phase and three
phase transformer, Single phase Transformers have single winding and three
phase transformers have three windings. These windings are connected in
connections such as star-delta, delta-delta, star-star connections. There is
another connection known as open delta connections, which consist of two
windings of transformers.
Open delta connections are done when one winding of
Transformer get faulty so as to continue the operation of Transformer but at
reduced load.
Open delta connections are as shown below:-
There are only two windings on both Transformer primary
and secondary sides.
Open delta connections are often known as V-V Connection
Transformers. Open delta connections are usually used to cater small loads.
Power Delivered by Open Delta connected Transformer:-
Power delivered by open delta connections in comparison
to 3-winding Transformers is about 57.7% of power delivered by Three winding
Transformers.
Calculations for the same as shown below:-
From Figure above you can see that:-
In case of delta connections ILine = √3 X IPhase
And in Open delta connections ILine =
IPhase
Power delivered by Transformer in VA for Delta connection
will be = 3 VL X IPhase
In case of open delta connection power delivered by Transformers
in VA will be= √3
X VL X IPhase
Power delivered by open delta connected Transformer=
√3
X VL X IPhase
Power delivered by Delta connected Transformer 3 VL X IPhase
Now from both Power’s we get; Power output of open Delta
connections is 57.7% of Power delivered by delta connected power Transformer.
Advantages of
Open delta connections:-
Open delta Transformer connections have following advantages:-
1. These are used
where Three phase power load is lower as cost of 3-winding Transformer is very
higher.
2. When
Delta-delta connected transformer one winding get burnt than open delta
connections will restore supply but with reduced load.
Disadvantages
of Open Delta connections:-
With open
delta connections power factor of the system get reduced to 86.6%. When load connected
at Open delta Transformer is having power factor 1 , then system power factor
for open delta connection s will be 0.866.,But when there are delta connected
Transformer is connected to that load then system power factor will be 1 means
that of load.
this was so helpfull
ReplyDelete