Open Delta connections; V-V connections

Open Delta (V–V) Transformer Connection

In electrical systems, we generally use single-phase transformers (with one winding on each side) and three-phase transformers (with three windings on each side). These windings can be connected in different configurations such as star–delta, delta–delta, or star–star.



There is also a special type of connection known as the Open Delta Connection (also called V–V Connection). This method uses only two transformer windings instead of three.


What is an Open Delta (V–V) Connection?

  • In an open delta configuration, only two transformers are connected in a three-phase system, while the third transformer winding is absent (or removed due to a fault).

  • This connection is often used as a temporary solution when one transformer in a delta–delta bank fails, allowing the system to continue supplying power but at reduced capacity.

  • Open delta transformers are also used for supplying small three-phase loads where installing a full three-transformer bank is uneconomical.


Circuit Representation



  • Delta–Delta Transformer Connection (3 windings)

  • Open Delta (V–V) Transformer Connection (2 windings)


Power Delivered by Open Delta Connection



For a Delta Connection:

Iline=3IphaseI_{line} = \sqrt{3} \, I_{phase} PĪ”=3VLIphaseP_{\Delta} = 3 \, V_{L} \, I_{phase}

For an Open Delta (V–V) Connection:

Iline=IphaseI_{line} = I_{phase} PVV=3VLIphaseP_{V-V} = \sqrt{3} \, V_{L} \, I_{phase}

Therefore,

PVVPĪ”=33=0.577(57.7%)\frac{P_{V-V}}{P_{\Delta}} = \frac{\sqrt{3}}{3} = 0.577 \, (57.7\%)

šŸ‘‰ Hence, an open delta connection delivers only 57.7% of the power that a closed delta connection would deliver.


System Power Factor

  • In open delta, when the load power factor = 1, the system power factor reduces to 0.866.

  • In a closed delta, the system power factor remains equal to the load power factor.


Advantages of Open Delta Connection

  1. Cost-effective for small loads – Instead of using three transformers, only two are required.

  2. Continuity of supply – If one transformer of a delta–delta bank fails, the system can continue operation in open delta mode (with reduced load capacity).


Disadvantages of Open Delta Connection

  1. Reduced capacity – Delivers only 57.7% of the original delta-connected transformer’s power.

  2. Reduced power factor – System power factor falls to 0.866 even if load has unity power factor.

  3. Not suitable for large loads – Due to limitations in power delivery and system efficiency.


Comparison Table: Delta vs. Open Delta

Parameter

Delta Connection (Ī”–Ī”)

Open Delta (V–V)

Number of Transformers

3

2

Power Delivered

100%

57.7%

System Power Factor (pf=1)

1.0

0.866

Application

Large Loads

Small Loads / Emergency use


Applications of Open Delta Connection

  • Temporary supply during failure of one transformer in a delta–delta bank.

  • Economical solution for supplying small three-phase loads.

  • Rural and remote areas where power demand is limited

Comments

Post a Comment

Popular posts from this blog

A2XWY; A2XFY Cables meaning; XLPE cables advantages over PVC cables

YWY, AYFY, AYY, AYCY, A2XCY Cables Meanings

Cable size and current carrying capacity