The rated
short-circuit making capacity of a circuit-breaker is the value of
short-circuit capacity assigned to that circuit-breaker by the manufacturer for
the rated operational making voltage at rated frequency and at a specified
power factor for A.C., or time constant for D.C. It is expressed as the maximum
prospective peak current. For a c the rated short-circuit making capacity of a
circuit-breaker shall be not less than its rated ultimate short-circuit breaking
capacity, multiplied by the factor n of table as below .
For d c the
rated short-circuit making capacity of a circuit-breaker shall be not less than
its rated ultimate short-circuit breaking capacity. A rated short-circuit
making capacity implies that the circuit-breaker shall be able to make the current
corresponding to that rated capacity at the appropriate applied voltage related
to the rated operational voltage.
Rated short-circuit breaking capacities
In
case of circuit breakers rated Short-Circuit capacity is the values of
short-circuit breaking capacity of that circuit-breaker assigned by the
manufacturer for the rated operational voltage, under specified conditions.
A
rated short-circuit breaking capacity requires that the circuit-breaker shall
be able to break any value of short-circuit current up to and including the
value corresponding to the rated capacity at a power-frequency recovery voltage
corresponding to the prescribed test voltage values and:
a) For alternating current at any power factor
not less than as per table below;
b) For
direct current, with any time constant not greater than as per table given
above.
For
power-frequency recovery voltages in excess of the prescribed test voltage
values , no short-circuit breaking capacity is guaranteed
Now what are Power frequency recovery
voltages?
All
tests shall be made at the rated frequency of the circuit-breaker. For all
short-circuit tests, if the rated breaking capacity is essentially dependent on
the value of the frequency, the tolerance shall not exceed +-5%. If the manufacturer declares the rated
breaking capacity to be substantially unaffected by the
value
of the frequency, the tolerance shall not exceed +-25 %.
For
alternating current the circuit-breaker shall be capable of breaking a
prospective current corresponding to its rated short-circuit breaking capacity
and the related power factor given in table above, irrespective of the value of
the inherent D.C. component, on the assumption that the AC, component is
constant.
Definitions:-
(a)
Rated service short-circuit breaking
capacity of a circuit-breaker
A breaking
capacity for which the prescribed conditions according to a specified test
sequence include the capability of the circuit-breaker to carry its rated
current continuously
(b)
Ultimate
short circuit breaking capacity of circuit breaker:-
A breaking
capacity for which the prescribed conditions according to a specified test
sequence do not include the capability of the circuit-breaker to carry its
rated current continuously
The rated short-circuit breaking
capacities are stated
as
(i)
Rated ultimate short-circuit breaking
capacity;
(ii)
Rated service short-circuit breaking
capacity.
(i)
Rated ultimate short-circuit breaking
capacity (Icu)
The
rated ultimate short-circuit breaking capacity of a circuit-breaker is the value
of ultimate short-circuit breaking capacity assigned to that circuit-breaker by
the manufacturer for the corresponding rated operational voltage. It is
expressed as the value of the prospective breaking current, in kA (RMS. value
of the a.c. component in the case of a,c. ),
(ii)
Rated service short-circuit breaking
capacity (Ics.)
The rated service short-circuit breaking capacity of
a circuit-breaker is the value of service short-circuit
breaking capacity assigned to that circuit-breaker by the manufacturer for the
corresponding rated operational voltage. It is expressed as a value of prospective
breaking current, in kA, corresponding to one of the specified percentages of
the rated ultimate short-circuit breaking capacity, in accordance with table as
given below, and rounded up to the nearest whole number. It may be expressed as
a % of Icu (for example Ics = 25 % Icu).
Alternatively,
when the rated service short-circuit breaking capacity is equal to the rated
short-time withstand current , it may be stated as that value, in kA, provided
that it is not less than the relevant minimum value of table as below.
Where
Icu exceeds 200 kA for utilization
category A, or 1000 kA for utilization category B, the manufacturer may declare
a value Ics of 50 kA.
Standard
relationship between short-circuit making and breaking capacities and related
power factor, for a.c. circuit-breakers
The standard relationship between short-circuit
breaking capacity and short-circuit making capacity is as given in table below.
The
rated short-circuit making and breaking capacities are only valid when the
circuit-breaker is operated in accordance with the requirements as given below
in Operating conditions of circuit breakers. For special
requirements, the manufacturer may assign a value of rated short-circuit making
capacity higher than that required by table above. Tests to verify these rated
values shall be the subject of agreement between manufacturer and user.
Rated
short-time withstand current (Icw)
The
rated short-time withstand current of a circuit-breaker is the value of
short-time withstand
current
assigned to that circuit-breaker by the manufacturer under the test conditions
For
A.C., the value of this current is the R.M.S value of the A.C. component of the
prospective short-circuit current, assumed constant during the short-time
delay.
The
short-time delay associated with the rated short-time withstand current shall
be at least 0.05 s, preferred values being as follows:
0.05
–0.1 –0.25–0.5–1 S
The
rated short-time withstand current shall be not less than the appropriate
values shown in table above
Operating
Conditions of Circuit breakers
(a)
Closing
For a
circuit-breaker to be closed safely on to the making current as a neutral pole,
then all corresponding to its rated short-circuit
making capacity, it is essential that it should be operated with the same speed
and the same firmness as during the type test for proving the short-circuit
making capacity.
(i)
Dependent manual closing
For a
circuit-breaker having a dependent manual closing mechanism, it is not possible
to assign a short- circuit making capacity rating irrespective of the
conditions of mechanical operation.
Such a
circuit-breaker should not be used in circuits having a prospective peak making
current exceeding 10 kA. However, this does not apply in the case of a
circuit-breaker having a dependent manual closing mechanism and incorporating
an integral fast-acting opening release which causes the circuit-breaker to
break safely, irrespective of the speed and firmness with which it is closed on
to prospective peak currents exceeding 10 kA; in this case, a rated
short-circuit making capacity can be assigned,
(ii)
Independent manual closing
A
circuit-breaker having an independent manual closing mechanism can be assigned
a short-circuit making capacity rating irrespective of the conditions of
mechanical operation.
(iii)
Dependent power closing
The
power-operated closing mechanism, including intermediate control relays where necessary,
shall be capable of securing the closing of the circuit-breaker in any
condition between no-load and Its rated making capacity, when the supply
voltage, measured during the closing operation, remains between the limits of
110 “A and 85 ‘A of the rated control supply voltage, and, when a c., at the
rated frequency.
At 110 % of
the rated control supply voltage, the closing operation performed on no-load
shall not cause any damage to the circuit-breaker.
At 85 “A of
the rated control supply voltage, the closing operation shall be performed when
the current established by the circuit-breaker is equal to its rated making
capacity within the limits allowed by the operation of its relays or releases
and, if a maximum time limit is stated for the closing operation, !n a time not
exceeding this maximum time limit.
(iv)
Independent
power closing
A circuit-breaker
having an independent power closing operation can be assigned a rated short-circuit
making capacity irrespective of the conditions of power closing. Means for
charging the operating mechanism, as well as the closing control components,
shall be capable of operating In accordance with the manufacturer’s
specification.
(v)
Stored energy closing
This type of
closing mechanism shall be capable of ensuring closing of the circuit-breaker
in any condition between no-load and its rated making capacity. When the stored
energy is retained within the circuit-breaker, a device shall be provided which
Indicates when the storing mechanism is fully charged, Means for charging the
operating mechanism, as well as the closing control components, shall be
capable of operating when the auxiliary supply voltage is between 85%.
and 110 % of
the rated control supply voltage. It shall not be possible for the moving
contacts to move from the open position unless the charge is sufficient for
satisfactory completion of the closing operation. When the energy storing
mechanism is manually operated, the direction of operation shall be Indicated This
last requirement does not apply to circuit-breakers with an independent manual
closing operation.
(b)
Opening
(i)
General
Circuit-breakers
which open automatically shall be trip-free and, unless otherwise agreed between
manufacturer and user, shall have their energy for the tripping operation
stored prior
to the
completion of the closing operation,
(ii)
Opening by over-current releases
Opening under
short-circuit conditions The short-circuit release shall cause tripping of the
circuit-breaker with an accuracy of +-20% of the tripping current value of the
current setting for all values of the current setting of the short-circuit
current release. Where necessary for over-current co-ordination , the manufacturer
shall provide Information (usually curves) showing
àmaximum cut-off
(let-through) peak current as a function
of prospective current (r, m.s. symmetrical); à /2t characteristics for
circuit-breakers of utilization category A and, if applicable, B for
circuit-breakers with instantaneous override.
Conformity with this information may be
checked during the relevant type tests in test sequences
II and Ill
(iii) Opening under overload conditions
1) Instantaneous or definite time-delay operation
The release
shall cause tripping of the circuit-breaker with an accuracy of+-10%
of the tripping current value of the current setting for
all values of current setting of the overload release.
2) Inverse time-delay operation
At the reference
temperature and at 1.05 times the current setting, i.e. with the conventional
non-tripping current, the opening release being energized on all phase poles,
tripping shall not occur in less than the conventional time from the cold
state, i.e. with the circuit-breaker at the reference temperature. Moreover,
when at the end of the conventional time the value of current is immediately
raised to 1.30 times the current setting, i.e. with the conventional tripping
current, tripping shall then occur in less than the conventional time later.
If a release
is declared by the manufacturer as substantially independent of ambient temperature,
the current values of table 6 shall apply within the temperature band declared
by the manufacturer, within a tolerance of 0.3%/K.
The
width of the temperature band shall be at least 10K on either side of reference
temperature.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.