NFPA – National Fire protection association 70
is also known as National Electrical Code
Examination, Identification, Installation, and
Use of Equipment as per NFPA 70:-
(i)
Examination:-
In judging equipment, considerations such as the following shall
be evaluated:
(1) Equipment usage can be
identified by an equipment description either marked on the product or by
description provided with a product to identify the suitability of the product
for a
(a)
Specific
purpose,
(b)
Environment,
or
(c)
Application
Conditions required for its usage and limitations or other
pertinent information may be marked on the equipment, included in the product
instructions, or included in the appropriate listing and labeling information.
Suitability of equipment may be evidenced by listing or labeling.
(2) Mechanical strength and durability, including, for parts designed
to enclose and protect other equipment, the adequacy of the protection thus
provided
(3) Wire-bending and connection space
(4) Electrical insulation
(5) Heating effects under normal conditions of use and also under
abnormal conditions likely to arise in service
(6) Arcing effects
(7) Classification by type, size, voltage, current capacity, and
specific use
(8) Other factors that contribute to the practical safeguarding of
persons using or likely to come in contact with the equipment
(B) Installation and Use:-
Listed or labeled equipment shall be installed and used in
accordance with any instructions included in the listing or labeling.
Voltages:-
Throughout this Code, the voltage considered shall be that at which the circuit
operates. The voltage rating of electrical equipment shall not be less than the
nominal voltage of a circuit to which it is connected.
Conductors:-
Conductors normally used to carry current shall be of copper
unless otherwise provided in this Code. Where the conductor material is not specified, the material and
the sizes given in this Code shall apply to copper conductors. Where other materials are used,
the size shall be changed accordingly.
Conductor Sizes:-
Conductor sizes are expressed in American Wire Gage (AWG) or in
circular mils.
Wiring Integrity:-
Completed wiring installations shall be free from short circuits,
ground faults, or any connections to ground other than as required or permitted
elsewhere in this Code.
Wiring Methods:-
Only wiring methods recognized as suitable are included in this Code. The recognized
methods of wiring shall be permitted to be installed in any type of building or
occupancy, except as otherwise provided in this Code.
Interrupting Rating:-
Equipment intended to interrupt current at fault levels shall have
an interrupting rating not less than the nominal circuit voltage and the
current that is available at the line terminals of the equipment. Equipment
intended to interrupt current at other than fault levels shall have an
interrupting rating at nominal circuit voltage not less than the current that
must be interrupted.
Circuit Impedance, Short-Circuit Current Ratings, and Other
Characteristics:-
The overcurrent protective devices, the total impedance, the equipment short-circuit current ratings, and
other characteristics of the circuit to be protected shall be selected and
coordinated to permit the circuit protective devices used to clear a fault to do
so without extensive damage to the electrical equipment of the circuit. This
fault shall be assumed to be either between two or more of the circuit
conductors or between any circuit conductor and the equipment grounding
conductor.
Deteriorating Agents:-
Unless identified for use in the operating environment, no
conductors or equipment shall be located in damp or wet locations; where
exposed to gases, fumes, vapors, liquids, or other agents that have a deteriorating
effect on the conductors or equipment; or where exposed to excessive
temperatures.
Equipment not identified for outdoor use and equipment identified
only for indoor use, such as “dry locations,” “indoor use only,” “damp
locations,” or enclosure Types 1, 2, 5, 12, 12K, and/or 13, shall be protected
against damage from the weather during construction.
Mechanical Execution of Work:-
Electrical equipment shall be installed in a neat and workmanlike
manner.
(A) Unused Openings. Unused openings, other than those intended for the operation of
equipment, those intended for mounting purposes, or those permitted as part of
the design for listed equipment, shall be closed to afford protection
substantially equivalent to the wall of the equipment. Where metallic plugs or
plates are used with nonmetallic enclosures, they shall be recessed at least 6
mm (1⁄4 in.) from the outer surface of the enclosure.
(B) Integrity of Electrical Equipment and Connections.
Internal parts of electrical equipment, including busbars, wiring
terminals, insulators, and other surfaces, shall not be damaged or contaminated
by foreign materials such as paint, plaster, cleaners, abrasives, or corrosive
residues.
There shall be no damaged parts that may adversely affect safe
operation or mechanical strength of the equipment such as parts that are
broken; bent; cut; or deteriorated by corrosion, chemical action, or
overheating.
(i)
ELECTRICAL
EQUIPMENTS MOUTING AND COOLING AS PER NFPA 70
(a) Mounting of electrical equipment’s:-
Electrical equipment shall be mounted
firmly and secured on to the surface on which it is required to be mounted.
There is an old practice of mounting electrical equipment’s using wooden plugs
which were mounted in holes of masonry, Concrete, plaster or similar material
this practice should not be used.
(b) Cooling
of electrical equipment’s:-
The electrical equipment’s which required sufficient natural air
circulation for not getting heated up should be installed in such a way that
room airflow over such equipment’s could not get restricted either by wall or
by adjacent equipment. The equipment’s which were designed for floor mounting
i.e. that directly mounted on trenches should have clearance between top
surface and adjacent surfaces so as to dissipate heat generated from
equipment’s.
There will be equipment’s which have ventilation openings shall be
installed in such way that there will
not be any obstructions to free circulation of air through the
equipment.
(ii)
Electrical
Connections.
There are different characteristics of different metals and we
should not mix conductors of dissimilar metals in a terminal or splicing connector
where there is contact occurs between dissimilar conductors such as:-
(a) Copper and aluminum
(b) Copper and copper-clad aluminum
(c) Aluminum and copper-clad aluminum
When there is requirement of using solder, Fluxes, Inhibitors and
Compounds then it must be kept in mind that they may not cause adverse effect
on conductors, Installations or equipment.
(A) Terminals:-
Connections of conductors to the terminal parts should ensure good
connection. Connections should not cause damage to the conductors. Connections
to the conductors should be done by means of :-
(i)
Hydraulic
punching machine
(ii)
Pressure
connectors
(iii)
Solder lugs
(iv)
Splices to flexible
leads.
(B) Splices:-
Conductors shall be spliced or joined with splicing devices by means
of
(i)
Brazing,
(ii)
Welding, or
(iii)
Soldering
with a fusible metal or alloy.
Soldered splices shall first be spliced or joined so as to be
mechanically and electrically secure without solder and then be soldered.
All splices and joints and the free ends of conductors shall be
covered with an insulation equivalent to that of the conductors or with an insulating
device identified for the purpose.
(C) Temperature Limitations:-
The temperature rating associated with the ampacity of a conductor
shall be selected and coordinated so as not to exceed the lowest temperature rating
of any connected termination, conductor, or device. Conductors with temperature
ratings higher than specified for terminations shall be permitted to be used
for ampacity adjustment, correction, or both.
Equipment Provisions:-
(i) For
Termination if there is circuit having rating 100 A or less , or marked for 14
AWG through 1 AWG conductors, shall be used only for one of the following:
(a) Conductors rated 60°C (140°F).
(b) Conductors with higher temperature ratings provided the ampacity
of such conductors is determined based on the 60°C (140°F) ampacity of the
conductor size used.
(c) Conductors with higher temperature ratings if the equipment is
listed and identified for use with such conductors.
(d) For motors marked with design letters B, C, or D, conductors having
an insulation rating of 75°C (167°F) or higher shall be permitted to be used,
provided the ampacity of such conductors does not exceed the 75°C (167°F)
ampacity.
(ii) Termination
provisions of equipment for circuits rated over 100 amperes, or marked for
conductors larger than 1 AWG, shall be used only for one of the following:
(a) Conductors rated 75°C (167°F)
(b) Conductors with higher temperature ratings, provided the ampacity
of such conductors does not exceed the 75°C (167°F) ampacity of the conductor
size used, or up to their ampacity if the equipment is listed and identified for
use with such conductors
Separate Connector Provisions:-
Separately installed pressure connectors shall be used with
conductors at the ampacities not exceeding the ampacity at the listed and identified
temperature rating of the connector.
(ii)High-Leg Marking:-
On a 4-wire, delta-connected system where the midpoint of one
phase winding is grounded, only the conductor or busbar having the higher phase
voltage to ground shall be durably and permanently marked by an outer finish
that is orange in color or by other effective means. Such identification shall
be placed at each point on the system where a connection is made if the grounded
conductor is also present.
(iii) Arc-Flash Hazard Warning:-
For electrical equipment’s such as:-
(a) Switchboard’s
(b) Panel-boards
(c) Industrial Control Panels
(d) Motor control centers
(e) Panels
There is need of routine examination, Maintenance while these
remains energized so there should be marking to warn the qualified person
against electrical flash hazard. The marking shall be located at such a place
that it should be clearly visible to qualified persons before examination,
adjustment, servicing, or maintenance of the equipment.
(iv) Arcing Parts
Parts of electrical equipment that in ordinary
operation produce arcs, sparks, flames, or molten metal shall be enclosed or
separated and isolated from all combustible material.
(v) Light and Power from Railway Conductors:-
Circuits for lighting and power shall not be connected to any system
that contains trolley wires with a ground return.
(vi) Marking:-
The manufacturer’s name, trademark, or other descriptive marking
by which the organization responsible for the product can be identified shall
be placed on all electrical equipment. Other markings that indicate voltage,
current, wattage, or other ratings shall be provided as specified elsewhere in
this Code.
The marking shall be of sufficient durability to withstand the environment
involved.
(vii)
Identification
of Disconnecting Means:-
(A)
General.
Each disconnecting means shall be legibly marked to indicate its
purpose unless located and arranged so the purpose is evident. The marking
shall be of sufficient durability to withstand the environment involved.
(B) Engineered Series Combination Systems.
Equipment enclosures for circuit breakers or fuses applied in
compliance with series combination ratings selected under engineering supervision
in accordance with 240.86(A) shall be legibly marked in the field as directed
by the engineer to indicate the equipment has been applied with a series
combination rating. The marking shall be readily visible and state the
following:
CAUTION — ENGINEERED SERIES COMBINATION
SYSTEM RATED _______ AMPERES. IDENTIFIED
REPLACEMENT COMPONENTS REQUIRED.
(C) Tested Series Combination Systems:-
Equipment enclosures for circuit breakers or fuses applied in compliance with the series
combination ratings marked on the equipment by the manufacturer in accordance
with 240.86(B) shall be legibly marked in the field to indicate the equipment
has been applied with a series combination rating. The marking shall be readily
visible and state the following:
CAUTION — SERIES COMBINATION SYSTEM
RATED ____ AMPERES. IDENTIFIED REPLACEMENT
COMPONENTS REQUIRED.
(viii)
Current
Transformers:-
Unused current transformers associated with potentially energized
circuits shall be short-circuited.
(ix) Available Fault Current:-
(A) Field Marking:-
Service equipment in other than dwelling units shall be legibly
marked in the field with the maximum available fault current. The field
marking(s) shall include the date the fault current calculation was performed and
be of sufficient durability to withstand the environment involved.
(B) Modifications:-
When modifications to the electrical installation occur that
affect the maximum available fault current at the service, the maximum
available fault current shall be verified or recalculated as necessary to
ensure the service equipment ratings are sufficient for the maximum available
fault current at the line terminals of the equipment. The required field marking
shall be adjusted to reflect the new level of maximum available fault current.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.