National Electricity code (NFPA 70) for working spaces while
installation of 600 V electrical equipments:-
In this article we will discuss about working
spaces of electrical equipment’s for voltage level of 600 Volts, Nominal, or
Less.
Spaces required for all Electrical Equipment:-
There should be sufficient Access and working space shall be
provided as to do the maintenance and operation of electrical equipment safely.
(A) Working Space:-
There should be due attention to be taken regarding working space
of equipment working at 600 Volts or less. This should comply with working
space requirement for examination , adjustment, servicing or maintenance. The
working spaces requirement will be shown in table as below:-
(i)
Depth
requirement of Working Space:-
The depth requirement of working space in the direction of live
parts shall not be less than that specified in table below unless the
requirements of all conditions are met as stated below . In These cases distances can be measured from the exposed
live parts or from the enclosure or from the opening if the live parts are
enclosed.
(a)
Dead-Front Assemblies:-
For dead front assemblies such as:-
à
Motor control centers
à
Switchboards
In these assemblies there will not be requirement of working space
in back sides.
In these assemblies all changing parts or adjustable parts such as
fuses or switches are accessible from other than back and back sides. Where
rear access is required to work on nonelectrical parts on the back of enclosed
equipment, a minimum horizontal working space of 762 mm (30 in.) shall be
provided.
(b)
Low Voltage:-
When there are exposed live parts having voltages in ranges
between 30 Volts RMS- 60 Volts RMS then working space requirement can be
reduced only by taking special permission.
(c)
Existing Buildings
If there is requirement of replacement of electrical equipment’s
in existing buildings then working space or clearance is per condition 2
mentioned in tables above for dead-front switchboards, panel-boards, or motor
control centers located across the passage. Where conditions of maintenance and
supervision ensure that written procedures have been adopted to prohibit equipment
on both sides of the passage from being open at the same time and qualified
persons who are authorized will service the installation.
(ii)
Working space
requirement across Width :-
The working space requirement across width in front of the
electrical equipment shall be the width of the equipment or 762 mm (30 in.),
whichever is greater. In all cases, the work space shall permit at least a 90 degree
opening of equipment doors or hinged panels; it is more advisable to have space
sufficient enough for opening of whole equipment as much allowable by hinge of
panel.
(iii)
Working space
requirement across Height:-
The working space requirement across height shall be clear and
extend from the grade, floor, or platform to a height of 2.0 m (61⁄2 ft)
or the height of the equipment, whichever is greater. Within the height
requirements of this section, other equipment that is associated with the
electrical installation and is located above or below the electrical equipment
shall be permitted to extend not more than 150 mm (6 in.) beyond the front of
the electrical equipment.
Exception No. 1: In existing residence
units, service equipment or panel-boards that do not exceed 200 amperes shall
be permitted in spaces where the height of the working space is less than 2.0 m
(61⁄2 ft).
Exception No. 2: Meters that are
installed in meter sockets shall be permitted to extend beyond the other
equipment. The meter socket shall be required to follow the rules of this
section.
(B) Clear Spaces:-
Working space required shall not be used for storage. When
normally enclosed live parts are exposed for inspection or servicing, the
working space, if in a passageway or general open space, shall be suitably
guarded.
(C) Entrance space requirement and Egress from Working Space:-
(i)
Minimum
Required:-
At least one entrance of sufficient area shall be provided to give
access to and egress from working space about electrical equipment.
(ii)
Large
Equipment:-
For an electrical equipment having ampere rating of 1200 amperes
or more and over 1.8 m (6 ft) wide that contains overcurrent devices, switching
devices, or control devices, there shall be one entrance to and egress from the
required working space not less than 610 mm (24 in.) wide and 2.0 m (61⁄2 ft)
high at each end of the working space. A single entrance to and egress from the
required working space shall be permitted where either of conditions stated
below are met:-
(a) Unobstructed Egress. Where the location permits a continuous and unobstructed way of egress
travel, a single entrance to the working space shall be permitted.
(b) Extra Working Space. Where the depth of the working space is twice that required by
table above, a single entrance shall be permitted. It shall be located such that
the distance from the equipment to the nearest edge of the entrance is not less
than the minimum clear distance specified in table above for equipment
operating at that voltage and in that condition.
(iii)
Personnel
Doors:-
When there are electrical equipment’s having rated current more
than 1200 A or more and also contains overcurrent devices, switching devices, or
control devices are installed and there is a personnel door(s) intended for
entrance to and egress from the working space less than 7.6 m (25 ft) from the
nearest edge of the working space, the door(s) shall open in the direction of
egress and be equipped with panic bars, pressure plates, or other devices that
are normally latched but open under simple pressure.
(iv)
Illumination:-
Illumination shall be provided for all working spaces about
service equipment, switchboards, panel- boards, or motor control centers
installed indoors and shall not be controlled by automatic means only.
(v)
Dedicated
Equipment Space:-
All switchboards, panel-boards, and motor control centers shall be
located in dedicated spaces and protected from damage.
Exception: Control equipment that by
its very nature or because of other rules of the Code must be adjacent to or
within sight of its operating machinery shall be permitted in those locations.
àIndoor:-
For indoor electrical equipment’s
(a)
Dedicated
Electrical Space:-
The
space equal to the width and depth of the equipment and extending from the
floor to a height of 1.8 m (6 ft) above the equipment or to the structural
ceiling, whichever is lower, shall be dedicated to the electrical installation.
No piping, ducts, leak protection apparatus, or other equipment foreign to the
electrical installation shall be located in this zone.
Exception: Suspended ceilings with
removable panels shall be permitted within the 1.8-m (6-ft) zone.
(b)
Foreign
Systems:-
The area above the dedicated space required shall be permitted to
contain foreign systems, provided protection is installed to avoid damage to
the electrical equipment from condensation, leaks, or breaks in such foreign
systems.
(c)
Sprinkler
Protection:-
Sprinkler
protection shall be permitted for the dedicated space where the piping complies
with this section.
(d)
Suspended
Ceiling:-.
A dropped, suspended, or similar ceiling that does not add
strength to the building structure shall not be considered a structural
ceiling.
à Outdoor:-
Outdoor electrical equipment shall be installed in suitable
enclosures and shall be protected from accidental contact by unauthorized
personnel, or by vehicular traffic, or by accidental spillage or leakage from
piping systems. The working clearance space shall include the zone. No
architectural appurtenance or other equipment shall be located in this zone.
(vi)
Locked Electrical
Equipment Rooms or Enclosures:-
Electrical equipment rooms or enclosures housing electrical apparatus
that are controlled by a lock(s) shall be considered accessible to qualified
persons.
No comments:
Post a Comment
Note: Only a member of this blog may post a comment.