CABLE TESTING USING A MEGGER
Purpose • Testing Procedure • Test Voltages •
Acceptable Values • Safety
1. What is a Megger and why is it used?
A Megger (insulation resistance tester)
applies a specified DC test voltage to electrical insulation and measures its
resistance, usually in megaohms (MΩ), gigaohms (GΩ) or higher.
·
Detect deteriorated, damaged,
wet or contaminated cable insulation.
·
Identify leakage paths between
conductors and earth.
·
Verify insulation condition
before energizing a newly installed cable.
·
Monitor insulation
deterioration during preventive maintenance.
·
Support investigation of
earth-leakage and insulation-related faults.
Important: A Megger measures insulation
resistance. It does not directly verify current-carrying capacity, conductor continuity,
phase sequence or the cable’s ability to withstand every operating surge.
2. Step-by-step cable testing procedure
Step
1 — Isolate the cable: Switch off and isolate the
cable from every source. Apply lockout/tagout (LOTO) and verify absence of voltage
with an approved voltage detector. Follow the site electrical safety procedure.
Step
2 — Disconnect sensitive equipment: Disconnect the
cable from PLCs, electronic equipment, VFDs, LED drivers, surge protection
devices and other components that could be damaged by the test voltage. Isolate
both ends wherever required.
Step
3 — Select the test voltage: Choose the DC test
voltage according to cable rated voltage, insulation type, applicable standard
and the manufacturer’s instructions. Do not automatically use 1000 V on every
cable.
Best Insulation Tester Buy Here Click on Image or Link
Step
4 — Test each core to earth: Connect the Megger
LINE (+) lead to the conductor under test and the EARTH (−) lead to a suitable
earth reference such as the cable screen or armour, as specified by the test
procedure. Keep other conductors grounded as required by the approved method.
Step
5 — Test between conductors: For multicore cables,
test each required conductor-to-conductor combination. For a three-phase cable,
this may include R–Y, Y–B and B–R, as well as phase-to-neutral tests where
applicable.
Step
6 — Record the reading: Record the cable ID, test
voltage, test duration, resistance, temperature and test conditions. A
one-minute reading is commonly used when specified by the applicable procedure.
Step
7 — Discharge the cable: Allow the tester’s
discharge function to operate, then discharge and earth the cable using the
approved method. Long cables can retain stored charge. Verify safe conditions
before touching conductors or reconnecting equipment.
3. Common DC test voltages
The values below are common starting points
only. The applicable standard, cable manufacturer and approved project/site
procedure take precedence.
|
Cable / circuit type |
Common DC test voltage |
|
SELV / PELV circuits |
250 V |
|
230/415 V low-voltage circuits |
500 V |
|
LV power cables where procedure permits |
500–1000 V |
|
3.3 kV / 6.6 kV / 11 kV cables |
Often 2.5–5 kV,
subject to cable-specific procedure |
|
Higher-voltage cables |
Specialist
test plan and manufacturer guidance |
Caution: For MV/HV cables, do not select
test voltage from this table alone. XLPE cables require cable-specific
procedures; insulation-resistance testing is not a substitute for appropriate
VLF, withstand or diagnostic tests.
4. Minimum insulation resistance values
IEC 60364-6:2016 provides the following
minimum values for general low-voltage installation verification. These are
installation verification thresholds, not universal acceptance criteria for
every isolated power cable.
|
Nominal circuit voltage |
DC test voltage |
Minimum insulation resistance |
|
SELV / PELV |
250 V |
0.5 MΩ |
|
Up to and including 500 V |
500 V |
1 MΩ |
|
Above 500 V |
1,000 V |
1 MΩ |
A healthy new cable may measure far above
these minimums. The required acceptance value must be taken from the applicable
cable standard, project specification or manufacturer. There is no single
resistance value that proves every cable is perfect.
5. Practical interpretation of readings
·
High and stable reading — Generally
encouraging. Compare with the commissioning baseline and previous readings taken
under similar conditions.
·
Low or falling reading — Investigate
moisture, dirt, damaged insulation, poor terminations, connected equipment and
temperature differences.
·
Below the required minimum, unstable or near-zero reading — Do not energize until the cause is investigated, corrective action
is completed and the cable passes specified tests.
A reading of 100 MΩ is not automatically
proof of safety compared with every 10 MΩ reading. Cable length, temperature,
insulation material and test setup matter. A sudden decline from the
established baseline warrants investigation.
6. Example: 3-phase, 415 V cable test matrix
Example only: a disconnected four-core
cable containing R, Y, B and N conductors, with armour connected to the earth
reference. Confirm the exact connections against the approved site procedure.
|
Test |
Connection (example) |
Purpose |
|
R–Earth |
R to LINE;
earth reference to EARTH |
R-core
insulation to earth |
|
Y–Earth |
Y to LINE; earth
reference to EARTH |
Y-core insulation to
earth |
|
B–Earth |
B to LINE; earth
reference to EARTH |
B-core
insulation to earth |
|
N–Earth |
N to LINE; earth
reference to EARTH |
Neutral insulation
to earth |
|
R–Y |
R to LINE; Y
to EARTH |
Insulation
between phases |
|
Y–B |
Y to LINE; B to
EARTH |
Insulation between
phases |
|
B–R |
B to LINE; R
to EARTH |
Insulation
between phases |
|
Phase–N |
Each phase tested
against N |
Insulation between
phase and neutral |
For a 415 V circuit, 500 V DC is a common
installation-test setting when permitted by the approved procedure. Disconnect
connected loads and sensitive devices first.
7. Illustrative test report
The values below are illustrative only and
are not actual measurements or guaranteed acceptance criteria.
|
Test combination |
Reading at 500 V DC |
Example assessment |
|
R–Earth |
250 MΩ |
Encouraging |
|
Y–Earth |
220 MΩ |
Encouraging |
|
B–Earth |
245 MΩ |
Encouraging |
|
N–Earth |
300 MΩ |
Encouraging |
|
R–Y |
400 MΩ |
Encouraging |
|
Y–B |
380 MΩ |
Encouraging |
|
B–R |
410 MΩ |
Encouraging |
These readings are high and reasonably
consistent. Final acceptance still depends on the applicable cable specification,
test duration and any other required tests.
8. Factors affecting Megger readings
·
Cable length: longer cables can
show different measured resistance and charging behaviour.
·
Temperature: insulation
resistance generally falls as temperature rises. Compare at similar
temperatures or apply the appropriate correction factor.
·
Moisture and contamination:
water, dirt and damp terminations can reduce readings.
·
Insulation material: PVC, XLPE
and other insulation materials have different properties.
·
Test duration: record readings
at the specified time and compare like-for-like results.
·
Connected equipment: loads,
electronics and surge protection can distort results or be damaged by test
voltage.
9. Final checklist before energizing
☐ Cable isolated and absence of voltage
verified.
☐ Cable ends and connected equipment
appropriately disconnected.
☐ Correct Megger test voltage selected.
☐ Core-to-earth insulation resistance
measured.
☐ Core-to-core insulation resistance
measured as required.
☐ Readings recorded and checked against
approved acceptance criteria.
☐ Cable safely discharged after testing.
☐ Conductor continuity, earthing, phase
identification and other required commissioning tests completed.
☐ All connections restored, inspected and
cleared for energization.
10. Engineering conclusion and references
A good cable should meet the specified
minimum insulation resistance, show no abnormal variation between comparable
cores, and produce stable results consistent with its baseline. A Megger
reading alone cannot certify a cable as completely fault-free.
Further reading:
·
Megger — Cable insulation test
voltages:
https://www.megger.com/en-ca/et-online/june-2019/cable-insulation-test-voltages-how-high-is-too-hig
·
Megger — Seven tips for
insulation resistance testing:
https://www.megger.com/en/et-online/january-2015/seven-tips-for-insulation-resistance-testing
Standards note: The minimum values quoted
above are attributed to IEC 60364-6:2016 for general low-voltage installation
verification. Always verify the currently applicable edition, local
requirements and project specifications before testing.